3c - InstAllInG/AdjUstInG lEGs oR cAstERs:

To install legs or casters, slide leg or caster into the caster channel from the side of the
unit without the refrigeration system.

To adjust the legs or casters, loosen the two bolts and move leg or caster to desired
location, spacing between leg or caster not to exceed 48 inches. Leg or caster on each
end of the unit can not exceed 8 inches from the end of the cabinet (Figure 1).

NOTE: Kairak recommends to position legs or casters under the mullion when
possible.

3. InstAllAtIon

(cont.)

3d - coRd & PlUG:

All self-contained models are shipped standard with a NEMA 5-15P plug and 9 foot cord.
Select only a dedicated electrical outlet for power source.

NOTE: Do not under any circumstances, cut or remove the round grounding
prong from the plug, or use an extension cord.

3E - PoWER sUPPlY:

The supply voltage should be checked prior to connection to be certain that proper
voltage for the cabinet wiring is available (refer to the serial tag to determine correct unit
voltage, see page 1). Make connections in accordance with local electrical codes. Use
qualified electricians.

Use of a separate, dedicated circuit is required. Size wiring to handle indicated load and
provide necessary overcurrent protector in circuit (see amperage requirements on the
unit’s serial tag).