Legrand 6ATC 8 User Manual

Page 11

Advertising
background image

11

Evolution Series Poke-Thru Devices are UL Listed and Classified to U.S. and Canadian safety standards to the
following conditions:

The 8STC Poke-Thru Stem with the 8CTC or 8CT Service Head Fitting, and the 8ATCP, 8ATP, 8ATC or 8AT factory assembled
Poke-Thru devices are for use with 1-, 1 1/2-, or 2- hour rated unprotected reinforced concrete floors and 1-, 1 1/2-, or 2- hour
rated floors employing unprotected steel floor units and concrete topping (D900 Series Designs), or concrete floors with suspended
ceilings. (Fire resistive designs with suspended ceilings should have provisions for accessibility in the ceiling area below the Poke-
Thru fittings).

The assembled Poke-Thru stem and service fitting will not reduce the ratings of the floor assembly when the thickness and type
of concrete (required for the specific rating) are within the specified limits and the fittings are installed as specified:

1. Spacing – Minimum of 2' [610mm] OC and not more than one unit per 65 sq. ft. [6 m

2

] of floor area in each span.

2. Concrete – Minimum thickness of structural concrete topping of 2 1/4" [57mm] over metal deck or a minimum 3" [76mm]

thick reinforced concrete slab. Unit weight of concrete to be 110 to 155 pcf.

3. Installation – Mounted in a 8" [203mm] diameter hole in concrete per installation instructions accompanying

the fittings. For use with power circuits, data and/or audio/visual cables as tabulated below:

The “TC” suffix letters indicate that the device may be installed on tile or carpet covered concrete floors. The “T” suffix letter
indicates that the device is intended to be installed on a concrete floor, embedded into the tile covering.

Size

Solid

#24

.00032 sq. in. [.20645mm

2

]

#22

.00050 sq. in. [.32258mm

2

]

#14

.00323 sq. in. [2.08386mm

2

]

#12

.00512 sq. in. [3.30321mm

2

]

#10

.00815 sq. in. [5.25805mm

2

]

#8

.01296 sq. in. [8.36127mm

2

]

Copper Cross Sectional Area

of Commonly Used Conductors

NOTE: Use above values for solid or stranded conductors.

Max Copper

.0154 sq. in.

.0775 sq. in.

X-Section

[9.9

mm

2

]

[16.6

mm

2

]

Max #

(3) 12 AWG

(24) 14 AWG

Conductors

OUTER

CENTER

CHANNELS

CHANNEL

COPPER CROSS-SECTION

NOTE:

When using conductor sizes other than listed above, the aggregate cross-sectional area of
the copper conductors shall not exceed the cross-sectional areas listed.

CAUTION: Receptacle supplied with this Poke-Thru is not suitable for direct field wiring.

Contact manufacturer for replacement. Field modifications will void UL Listing
and Classification. Replacement receptacle is limited to this manufacturers'
Catalog No 68REC.

Advertising
This manual is related to the following products: