CB-7012, CB-7014, CB-7017 User’s Manual
1. Set the CB-7014D to read ±20 mA type.
Command: %01010D0600
Receive: !01
(Ref. Sec. 2.1 %AANNTTCCFF)
2. Set the source low value(SL)=4 and source high value (SH)=20.
Command: $016+04.000+20.000
Receive: !01
(Ref. Sec. 2.32 $AA6(SL)(SH))
3. Set the target low value (TL)=0 and target high value (TH)=100.
Command: $017+000.00+100.00
Receive: !01
(Ref. Sec. 2.33, $AA7(TL)(TH))
4. Enable linear mapping function.
Command: $01A1
Receive: !01
(Ref. Sec. 2.34, $AAAV)
We’ll read the temperature value from CB-7014D
directly using command #AA.