3. Installation

3-3

A050505-1



Never locate the unit with the exhaust muffler facing any
private house:

As the exhaust fume (gas) from the engine is poisonous,
never direct it to any other persons passing by.









The machine has to be installed on dry, firm, and level
area.

Avoid installing the machine in a place such as a damp
place or a place where puddles are apt to be formed
after rain. Such installation could cause electric shock.

When installing the machine at the sea shore or on a
ship, make sure that the machine should not be
exposed directly to sea water.

When installing the machine at a sandy place, make
sure that exhaust from the generator or radiator does
not blow the sand up in the air, or into the machine.

In case that the unit has to be installed inevitably on any
rough and uneven ground; it is necessary to insert
square wooden bars under the unit for levelling it.

The machine should be operated in following conditions:

Ambient temperature -15℃ to +40℃

Humidity

Less than 85%

Altitude

Lower than 500 m above sea level

If more than two machines are placed parallel in
operation, keep enough distance so that exhaust air
from one machine does not effect the other one.

Keep enough space around the unit for inspection and
maintenance access.



1000 or more

10

00 or mor

e

10

00 or mor

e

SG0110

Unit : mm

SG0103-1

How to locate the unit

×