5. Periodic Inspection/Maintenance

5-15

A070437

5.5.19 Check the terminal portion of electrical circuits and cable connections

[Every 4 months or every 500 hours]

Check for any looseness on the cables and any damages on insulated covers and disconnection,

disconnected cables, or short-circuit etc.

[Checking points of electrical circuits on the generator side]

Terminal connection of three-phase output

terminal plate.

Main circuit of circuit breaker.

Terminal connection on control box.

Each terminal connection of each

instrument.

[Checking points of electrical circuits on

the engine side]

Portion of connectors to the engine.

Check for looseness of terminal connections.

5.5.20 Check vibration isolator rubbers

[Every 1 year or every 1,000 hours]

The vibration isolation rubber “1” is used for

the support of generator and engine. Check
the rubber for any damage or deterioration
due to oil sticking.

1

Output terminal board

Circuit breaker

Looseness・Disconnection

Looseness

Disconnection

Looseness

Looseness

A080074