Installation, Continued, Mantel clearances – Desa CCL3018NR EN User Manual

Page 10

Advertising
background image

www.desatech.com

111161-01E

10

INSTALLATION

Continued

Figure 5 - Heat Resistant Material (Slate,

Marble, Tile, etc.) Above Fireplace

If Using Mantel
You must have noncombustible material(s) above

the fireplace opening. Noncombustible materials

(such as slate, marble, tile, etc.) must be at least

1/2 inch thick. With sheet metal, you must have

noncombustible material behind it. Noncombustible

material must extend at least 8 inches up (for all

models). If noncombustible material is less than

12", you must install the fireplace hood accessory

(24" and 30" models only). Even if noncombustible

material is more than 12", you may need the hood

accessory to deflect heat away from your mantel

shelf. See Figure 5 and Figures 6 and 7 on page 9

for minimum clearances.
IMPORTANT:

If you cannot meet these minimum

clearances, you must operate heater with chimney

flue damper open. Go to Installing Damper Clamp

Accessory for Vented Operation, page 11.

Noncombustible Requirements for
Material

Safe Installation

Distance (A)
12" or more

Noncombustible material

okay.

Between 8"

Install fireplace hood

and 12"

accessory (GA6050,

GA6052 or GA6053 see

Accessories, page 34).

Less than 8"

Noncombustible material

must be extended to at

least 8". See Between 8"

and 12", above. If you

cannot extend material,

you must operate heater

with flue damper open.

Heat Resistant
Material

(A)

MANTEL CLEARANCES

In addition to meeting noncombustible material

clearances, you must also meet required clearances

between fireplace opening and mantel shelf. If

you do not meet the clearances listed below, you

will need a hood.
Determining Minimum Mantel Clearances
If you meet minimum clearance between mantel

shelf and top of fireplace opening, a hood is not

required (see Figure 6).
Determining Minimum Mantel Clearances
When Using a Hood
If minimum clearances in Figure 6 are not met, you

must have a hood. When using a hood there are

still certain minimum mantel clearances required.

Follow minimum clearances shown in Figure 7,

page 11, when using hood.

NOTICE: Surface temperatures

of adjacent walls and mantels be-

come hot during operation. Walls

and mantels above the firebox

may become hot to the touch.

If installed properly, these tem-

peratures meet the requirements

of the national product standard.

Follow all minimum clearances

shown in this manual.

Figure 6 - Minimum Mantel Clearances

Without Using Hood

Minimum

Noncombustible

Material

Minimum

Noncombustible

Material Height

Distances to

Underside of

Mantel

Top of Fireplace

Opening

Underside

of Mantel

Shelf

Mantel Shelf

12"
8"

(A)

18"
8"

20"
14"

22"
17"

24"
20"

All minimum

distances

are in inches

Log Set
24"/30"

Models
18" Model

2

1/2

"

6"

8"

10"