Installation, Continued, Floor clearances – Desa CCL3018NR EN User Manual

Page 11

Advertising
background image

www.desatech.com

111161-01E

11

Minimum

Noncombustible

Material

8"

Min.

12"

15"

18"

All minimum

distances are

in inches

Log Set

18", 24",

30" Models

20"

2

1/2

"

6"

8"

10"

12"

Distances to

Underside of

Mantel

Hood

(GA6050,

GA6052)

Top of

Fireplace

Opening

Underside

of Mantel

Shelf

Mantel Shelf

INSTALLATION

Continued

Figure 7 - Minimum Mantel Clearances

When Using Hood

All
Models

NOTICE: If your installation does

not meet the minimum clear-

ances shown, you must do one

of the following:

• operate the logs only with the

flue damper open

• raise the mantel to an accept-

able height

• remove the mantel.

FLOOR CLEARANCES

A. If installing appliance on the floor level, you

must maintain the minimum distance of 14"

to combustibles (see Figure 8).

B. If combustible materials are less than 14" to

the fireplace, you must install appliance at

least 5" above the combustible flooring (see

Figure 9).

14"

Min.

Combustible

Material

Noncombustible Material

Hearth

5"

Min.

Combustible

Material

Figure 9 - Minimum Fireplace Clearances

Above Combustible Flooring

Figure 8 - Minimum Fireplace Clearances

If Installed at Floor Level

INSTALLING DAMPER CLAMP
ACCESSORY FOR VENTED
OPERATION

Note:

When used as a vented heater, appliance

must be installed only in a solid-fuel burning

fireplace with a working flue and constructed of

noncombustible material.
If you choose to use your heater as a manually-

controlled model (no remote control installed),

you may use this heater as a vented product. There

are three reasons for operating your heater in the

vented mode.
1. The fireplace does not meet the clearance

to combustibles requirements for vent-free

operation.

2. State or local codes do not permit vent-free

operation.

3. You prefer vented operation.
If reasons number 1 or 2 above apply to you, you

must permanently open chimney flue damper. You

must install the damper clamp accessory (to order,

see Accessories, page 34). This will insure vented

operation (see Figure 10, page 12). The damper

clamp will keep damper open. Installation instruc-

tions are included with clamp accessory.
See chart below for minimum permanent flue

opening you must provide. Attach damper clamp

so the minimum permanent flue opening will be

maintained at all times.

Chimney

Minimum Permanent

Height (ft.)

Flue Opening (sq. in.)

6' to 15'

39 sq. inches

15' to 30'

29 sq. inches

Area of Various Standard Round Flues

Diameter (inches)

Area (sq. inches)

5

20

6

29

7

39

8

51