Manual test of the UPS

Manual UPS or Manual Battery tests can be conducted from the UPS configuration as well and are
functional even when the UPS is not charging the battery.

Manual Battery test: Scroll the parameters until Manual Bat test displays on the LCD.

Press the button twice.

**) Note: In order for the UPS and power management software to operate normally, Manual Bypass should
always be set to OFF as the load will not be protected by the unit when Manual Bypass is ON. This is aimed
for operating an external maintenance bypass switch.

***) Note: You should turn UPS off and keep the AC power before you use

Generator

function. (even you

want to select

\Generator\OFF

to back to normal mode).

6.4 Interpreting UPS messages

Troubleshooting procedures described here give simple instructions in determining UPS malfunctions.

Start the troubleshooting procedure if you witness any alarm indication on the control panel.

Alarm indicators

The UPS gives the following audible alarms:

If UPS is on battery and the ON BATTERY LED is on, UPS will beep every 5 seconds.

If the battery capacity is low and the ON BATTERY LED is flashing, the UPS will beep twice every 5

seconds.

If UPS is on bypass and the BYPASSED LED is on, UPS will no beep.

If UPS has an internal fault and the ALARM LED is on, the UPS will give a constant audible alarm

displaying the cause on the LCD display.

Silencing an alarm

By pressing any of the three buttons on the front panel, the alarm can be turned off, except when the battery
is low, which will cause the alarm to resound.

On the LCD display, you can also choose silent alarm mode which will not warn you of any malfunction