11. Technical Specification

Specifications for 120V/277V

Capacity (W)

200W

300W

490W

Voltage

Single Phase 120Vac or 277V

Voltage Range

120Vac ±10% or 277V

Frequency

50Hz or 60Hz +/- 4Hz

Input

Power Factor

> 95%

Voltage (on battery)

Single Phase 120Vac or 277V

Voltage Range

120Vac ±2% or 277V

Frequency (on battery)

50 / 60 Hz +/-0.5%

Transfer Time

0 ms

Overload Recovery

Auto transfer to UPS

High Efficiency mode (AC to AC) > 95 %

Output

UPS Design Technology

On-Line / Fully digitized microprocessor controlled

Surge Protection

120V (IEEE C62.41) / 230V (IEEEC61000-4-5 level 3)

Overload Protection

125% for 1 minutes and 150% for 10 seconds

Protection and Filtering

Short Circuit Protection

Circuit breaker

Visual Display

(LED model)

UPS on(green), line-mode(green),

battery mode(yellow), bypass(yellow), fault(red)

Visual Display

(LCD model)

Input / output voltage, input / output frequency,

on-line mode, back up mode, battery capacity, load level

Audible Alarm

Beep every 5 sec

UPS Fault

Continuous beeping sound and LCD display

System/Display/ Warning

Communication

RS-232 Serial Port and USB

Battery

90 min.

2X35 A/H

2X50 A/H

2X50 A/H

Dimensions

Inches (width x Height x depth)

24 x 17 x 9.5

Note: Due to continuous improvement specifications are subject to change without prior notice