RSMV STATUS

VCC-X Operator Interface SD

68

Status Screen #3 - Coil (Suction Line)

Temperature 1, Superheat 1, and Expansion

Valve 1 Position

RSM #1-4 Status

Coil Tmp 1: 0.0ºF
Superheat 1: 0.0ºF
EXV 1 Pos: 0.0%

Line 2 Coil (Suction Line) Temperature 1

Current Coil (Suction Line) Temperature 1.

Line 3 Superheat 1

Current Superheat temperature for Expansion Valve 1.

Line 4 Expansion Valve 1 Position

Modulating position for Expansion Valve 1.

Status Screen 4 - Coil (Suction Line)

Temperature 2, Superheat 2, and Expansion

Valve 2 Position

RSM #1-4 Status

Coil Tmp 2: 0.0ºF
Superheat 2: 0.0ºF
EXV 2 Pos: 0.0%

Line 2 Coil (Suction Line) Temperature 2

Current Coil (Suction Line) Temperature 2.

Line 3 Superheat 2

Current Superheat temperature for Expansion Valve 2.

Line 4 Expansion Valve 2 Position

Modulating position for Expansion Valve 2.

Status Screen 5 - Head Pressure Setpoint and

Condenser Fan Signal

RSM #1-4 Status

Head Pr: 0psi
Setpoint: 0psi
Cond. Signal: 0.0%

Line 2 Head Pressure 1

If a Head Pressure Transducer is connected, this line

indicates the current Head Pressure reading.

Line 3 Head Pressure Setpoint

The current Head Pressure Setpoint.

Line 4 Condenser Signal

The current percentage signal being sent to

the Condenser Fan or Valve in order to maintain the

Head

Pressure

Setpoint.

Status Screen 6 - Low Suction Pressure Alarm,

Unsafe Suction Pressure Alarm, and High Head

Pressure Alarm

RSM #1-4 Alarms

Low Suction Pr.: NO
Unsafe Suct Pr.: NO
High Head Pr.: NO

Status Screen 7 - Compressor 1 Trip Alarm,

Compressor 2 Trip Alarm, No Head Pressure

Alarm

RSM #1-4 Alarms

Comp 1 Trip: NO
Comp 2 Trip: NO
No Head Pr.: NO

Status Screen 8 - No Suction Pressure Alarm,

Communication Timeout Alarm,

No Coil Temperature 1 Alarm

RSM #1-4 Alarms

No Suct Pr: NO
Comm Timeout.: NO
No Coil Tmp 1.: NO

Status Screen 9 - No Coil Temperature 2 Alarm,

Low Superheat 1 Alarm, Low Superheat 2 Alarm

RSM #1-4 Alarms

No Suct Pr: NO
Comm Timeout.: NO
No Coil Tmp 1.: NO

RSMV Status Screens