Minilink pd configuration, Minilink pd confi guration and status screens – Orion System VCC-X Controller User Manual
Page 80

Zone
Zone
MINILINK PD CONFIGURATION
80
VCC-X Operator Interface SD
MiniLink PD Confi guration and Status Screens
Confi guration Screen #4 - Optimal Start
Target Zone
Polling Unit Config
Optimal Start
Target Zone..: XXX
[Enter Target Zone]
This is the unit ID of the Zone that you want to be satisfi ed by the
normally scheduled start time. If you enter “-1” into this box, it will
average all zones instead of picking a specifi c zone. If you do not
require Optimal Start, enter “0”.
Confi guration Screen #5 - Maverick Testing
Polling Unit Config
Maverick Testing
Disabled: YES
Use < Or > To Change
Disabling the Maverick Testing allows known troubled zone(s) to
continue voting without causing a Maverick alarm. In other words,
all zones are included in the voting regardless of whether they are
more than four degrees from setpoint.
Confi guration Screens #6-65 - Alarm Polling
Polling Unit Config
Enable Alarm Polling
Unit XX : YES
Use < Or > To Change
Enabling Alarm Polling allows any alarm from the loop to be polled.
You must set this for each controller on the loop.
MiniLink PD Status
Status Screen #1 - Schedule Mode, System
Status, and Minutes Left
Polling Device
System Occupied
Venting Mode
XXX Min Left in Mode
Line 2 Current Schedule Mode
Can be System Occupied or System Unoccupied.
Line 3 Currently System Status
Can be Vent Mode, Cooling Mode, or Heat Mode.
Line 4 Minutes Left In Mode
The number of minutes left in the current mode of
operation before it can switch modes. This value is
user-adjustable.
See
Confi guration Screen #3.
Status Screen #2 - Mode Priority, Cool Total,
and Heat Total
Polling Device
No Mode Priority
Cool Total.: XX.XºF
Heat Total.: XX.XºF
Line 2 Mode Priority
Can be Heat Priority or Cool Priority. This is based
on the voting zones and their demand.
Line 3 Cool Total
Total cooling temperature demand from all zones.
Line 4 Heat Total
Total heating temperature demand from all zones.
- VCB-X Controller VCB-X VCB-X Modular Service Tool VCM Controller Operator Interfaces SD VCM-X/RNE Controller VCC-X Modular System Manager SD Modular System Manager SD Quick Start VCM-X/RNE Controller Operator Interface SD SA E-BUS Controller VAV II Controller v.1 CAV II Controller v.1 MUA II Controller v.1 VAV II Controller v.2 CAV II Controller v.2 MUA II Controller v.2