MINILINK PD CONFIGURATION

80

VCC-X Operator Interface SD

MiniLink PD Confi guration and Status Screens

Confi guration Screen #4 - Optimal Start

Target Zone

Polling Unit Config

Optimal Start

Target Zone..: XXX

[Enter Target Zone]

This is the unit ID of the Zone that you want to be satisfi ed by the
normally scheduled start time. If you enter “-1” into this box, it will
average all zones instead of picking a specifi c zone. If you do not
require Optimal Start, enter “0”.

Confi guration Screen #5 - Maverick Testing

Polling Unit Config

Maverick Testing

Disabled: YES

Use < Or > To Change

Disabling the Maverick Testing allows known troubled zone(s) to
continue voting without causing a Maverick alarm. In other words,
all zones are included in the voting regardless of whether they are
more than four degrees from setpoint.

Confi guration Screens #6-65 - Alarm Polling

Polling Unit Config

Enable Alarm Polling

Unit XX : YES

Use < Or > To Change

Enabling Alarm Polling allows any alarm from the loop to be polled.
You must set this for each controller on the loop.

MiniLink PD Status

Status Screen #1 - Schedule Mode, System

Status, and Minutes Left

Polling Device

System Occupied

Venting Mode

XXX Min Left in Mode

Line 2 Current Schedule Mode

Can be System Occupied or System Unoccupied.

Line 3 Currently System Status

Can be Vent Mode, Cooling Mode, or Heat Mode.

Line 4 Minutes Left In Mode

The number of minutes left in the current mode of

operation before it can switch modes. This value is

user-adjustable.

See

Confi guration Screen #3.

Status Screen #2 - Mode Priority, Cool Total,

and Heat Total

Polling Device

No Mode Priority

Cool Total.: XX.XºF
Heat Total.: XX.XºF

Line 2 Mode Priority

Can be Heat Priority or Cool Priority. This is based

on the voting zones and their demand.

Line 3 Cool Total

Total cooling temperature demand from all zones.

Line 4 Heat Total

Total heating temperature demand from all zones.