VAV/ZONE CONFIGURATION

VCC-X Operator Interface SD

72

VAV/Zone Setpoint Screens

VAV/Zone Controller Setpoints

Modular Service Tool Instructions

From any menu screen, press

<SETPOINTS>

. The Unit Selection

Screen, shown below,

will appear requesting that you enter the unit

ID number.

Enter Unit Address

Then Press Enter

Selected Unit #_1

Press Down

Enter

the correct unit ID number of the Controller you want to

change Setpoints for and press

<ENTER>

. Once communication is

established, the *00* message will go away. Then

press

<

>

. You

will then see Setpoint Screen #1. Press

<ENTER>

to save entered

data and

press

<

>

to scroll through the screens.

NOTE:

If the *00* remains, it indicates a communication

failure to the controller.

System Manager SD Instructions

From any Main screen, press

<SETPOINTS>

. The screen below

will appear because this option requires passcode clearance. Only a
Level 2 passcode can change setpoints.

THIS ACTION REQUIRES

PASSCODE CLEARANCE

Enter Passcode: XXXX

If the correct passcode was entered, the Unit Selection Screen will
be displayed.

Enter Unit Address

Then Press Enter

Selected Unit #_1

Press Down

Enter the Unit ID of the controller you wish to change setpoints for
and press

<ENTER>

. Once communication is established, the *00*

message will go away. Then

press

<

>

.

NOTE:

If the *00* remains, it indicates a communication

failure to the controller.

The following screen will be displayed:

Change Setpoints
Configure Unit

Save/Copy/Restore

Scroll to the ‘Change Setpoints’ option and press

<ENTER>

. This

will take you to the fi rst Setpoints Screen shown below.

Setpoint Screen #1 - Occupied Setpoints

XX Box Spts IDXXXX
Occupied Setpoints

Cooling.....: XXºF
Heating.....: XXºF

Enter the Occupied Cooling Setpoint as the maximum temperature
you would like the zone to reach before modulating the damper
open to bring in more cold air to cool the space. Enter the Occupied
Heating Setpoint
as the minimum temperature you would like the
zone to reach before activating the Reheat Stages on the optional
Expansion Relay board. If this is a Cooling Only box that doesn’t
contain reheat, this setpoint will be ignored.

Description

Minimum

Default

Maximum

Cooling Setpoint

50ºF

74ºF

90ºF

Heating Setpoint

50ºF

70ºF

90ºF

Setpoint Screen #2 - Unoccupied Setbacks

XX Box Spts IDXXXX

Unoccupied Setbacks

Cooling SetUp: XXºF
Heating SetBk: XXºF

During unoccupied hours, the Occupied Cooling Setpoint is adjusted
up by the amount entered for the Cooling SetUp. The Occupied
Heating Setpoint is adjusted down by the amount entered for the
Heating SetBk.

Description

Minimum

Default

Maximum

Cooling SetUp

0ºF

+10ºF

+30ºF

Heating SetBk

0ºF

-10ºF

-30ºF