Gbd-x wiring – Orion System GBD-X Controller User Manual

Page 7

Advertising
background image

Line

V

oltage

Warning

:

24 VAC Must Be Connected So That All Ground
Wires Remain Common. Failure To Do So Will
Result In Damage To The Controllers.

24V

AC

GND

Up to (6) CO Sensors Can Be
Used On The GBD-X.

AIN2, AIN3,

AIN4,

2

They Can

Be Wired To AIN1,

AIN5 And AIN7 As

Desired. Only 4-20mA CO
Sensor(s) May Be Used.

2

The Jumper For The Analog Input That
Each CO Sensor Is Connected To Must
Be Set For 4-20mA As Shown For Proper
Operation Of The GBD-X Controller.

2

24

V

AC

T

ransformer

8

V

A

Minimum

Typical Wiring
Shown For Input

AI1. Wiring For

Other Inputs Is
Identical.

AI1

AI1
SET

AI2
SET

AI3
SET

AI4
SET

AI5
SET

AI7
SET

AI2

AI3

AI4

AI5

AI7

FILENAME

DATE:

B. CREWS

DESCRIPTION:

PAGE

DRAWN BY:

OE332-23- GBDX Controller

JOB NAME

10/21/10

OE332-23-GBDX-Wire1A.CDR

FILENAME

JOB NAME

2 of 5

GBD-X Wiring

4.) All Wiring To Be In Accordance

With Local And National Electrical
Codes And Specifications.

3.) Set-up, Programming And

Monitoring Of The GBD-X
Controller Requires The Use Of A
Personal Computer And Prism
Software.

2.) 24 VAC Must Be Connected

So That All Ground Wires
Remain Common.

Notes:

1.) The GBD-X Can Either Be Used

With CO2 Sensors Or Space
Temperature Sensors But Not
Both On The Same GBD-X
Controller. Up to 2 GBD
Controllers Can Be Located On
Each Local Loop.

OE33 -2 -

GBD

Device Wiring

When Used For CO Applications

2

3 GBDX

-X

2

OE255 or OE256
CO Sensor
(4-20ma Signal)

2

24VAC

GND

Up to (6) CO Sensors Can Be
Used On The GBD-X.

AIN2, AIN3,

AIN4,

2

They Can

Be Wired To AIN1,

AIN5 And AIN7 As

Desired. Only 4-20mA CO
Sensor(s) May Be Used.

2

8
7
6
5
4

AC-/DC-

AC+/DC+

Jumper Can Be Set To 0-5 V
Or 0-10 V For 4-20 mA Operation
(Both Pins Covered Or 1 Pin)
On Jumper Terminals J3

SIGNAL

GND