OE210 Space Temperature Sensor

OE331-21-AVG

GBD Device Wiring

When Used For Space Temperature Sensor Averaging Applications

GND

TMP

FILENAME

DATE:

B. CREWS

DESCRIPTION:

PAGE

DRAWN BY:

OE332-23- GBDX Controller

JOB NAME

OE332-23-GBDX-Wire1A.CDR

FILENAME

JOB NAME

4 of 5

GBD-X Wiring

4.) All Wiring To Be In Accordance

With Local And National Electrical
Codes And Specifications.

3.) Set-up, Programming And

Monitoring Of The GBD-X
Controller Requires The Use Of A
Personal Computer And Prism
Software.

2.) 24 VAC Must Be Connected

So That All Ground Wires
Remain Common.

Notes:

1.) The GBD-X Can Either Be Used

With CO2 Sensors Or Space
Temperature Sensors But Not
Both On The Same GBD-X
Controller. Up to 2 GBD
Controllers Can Be Located On
Each Local Loop.

Line

V

oltage

Warning

:

24 VAC Must Be Connected So That All Ground
Wires Remain Common. Failure To Do So Will
Result In Damage To The Controllers.

24V

AC

GND

Up to (6) Space Temperature
Sensors Can Be Used On The
GBD-X.

AIN2, AIN3, AIN4,

They Can Be Wired To

AIN1,

AIN5

And AIN7 As Desired.

The Jumper For The Analog Input
That Each Space Temperature
Sensor Is Connected To Must Be Set
For Thermistor As Shown For Proper
Operation Of The GBD-X Controller.

24

V

AC

T

ransformer

8

V

A

Minimum

Typical Wiring
Shown For Input

AI1. Wiring For

Other Inputs Is
Identical.

AI1

AI1
SET

AI2
SET

AI3
SET

AI4
SET

AI5
SET

AI7
SET

AI2

AI3

AI4

AI5

AI7

10/21/10