Description

The OE332-23-GPCX GPC-X Controller
is used for controlling equipment or
processes that cannot be controlled us-
ing a standard HVAC controller. The
Prism computer front end software is
used to interface with the GPC-X control-
ler functions. The GPC-X Controller pro-
vides the flexibility to control, schedule
and/or monitor equipment such as unit
heaters, exhaust fans, motorized lou-
vers, and other mechanical equipment.
The GPC-X has (6) configurable inputs
which will accept signals from thermistor
temperature sensors, 4-20mA or 0-
5VDC or 0-10VDC transmitters or dry
contact closures. The inputs are set for
the desired input by means of a jumper
bar. An additional modular input is pro-
vided for connection of an OE271 static
pressure sensor. The GPC-X has (5)
relay outputs for on/off control and (2)
analog outputs. With the addition of the
OE358-23-12R, 12 Relay Expansion
Module, (4) additional relay outputs (of
the 12 total relays on the module) are
available for use with the GPC-X, provid-
ing for a maximum of (9) usable relay
outputs total. The GPC-X also has (5)
separate 2 event per day schedules,
each with its own optimal start functions
built in. In addition the GPC-X provides
lead/lag start capabilities.

Mounting

The GPC-X is provided with an integral plastic enclosure which provides mounting points for mounting inside of a
control enclosure. It is recommended that the GPC-X be mounted in a control enclosure in the building equip-
ment room. An optional factory control enclosure for the GPC-X is also available.

OE332-23-GPCX

GPC-X Controller




Technical Data

OE332-23-GPCX GPC-X Controller

Power

24 Volt AC

Weight

1.5 lb.

Power Consumption

8 VA Maximum

Network Connection

RS-485

Operating Temp

10

°F to 149°F Protocol

HSI Open Protocol Token Passing

Operating Humidity

90% RH Non-Condensing

Communications

RS-485 - 9600 Baud

Inputs:

Outputs:

Type III-10kohm sensors

Total Relay Qty. On Board

5

4-20ma

0-5VDC & 0-10VDC

Total Relay Qty. Available With
Optional Expansion Board

9

Types of Allowed
Inputs

N.O. or N.C. Binary Contact

Relay Power Rating

(2 Amp @ 24 VAC)

Total Inputs Available

7

Analog Output Qty.

2

Static Pressure Inputs

1 (Modular )

Analog Output Signal

0-10 VDC

Configurable Inputs

6

Optimal Start Schedules

(5) Total - (1) for Each Schedule

Schedules Available

(5) 2 Event per day

Lead Lag Scheduling

(1) Output can be Configured

Three Year Warranty