Description

The OE332-23-GBDX General Broadcast Device
Controller provides a method of connecting up to
a maximum of (6) Thermistor 10 K Ohm Room
Temperature Sensors (OE210, OE211, OE212,
and OE213) so that they can then be averaged
and globally broadcast to one VCM-X controller
on a local loop. The GBD-X also includes the
ability to read up to (6) CO

2

Sensors—4-20 ma

(OE255 and OE256) and/or 0-5VDC (by oth-
ers)— and average or find the highest reading
and then broadcast the reading to one VCM-X
controller on a local loop. It also provides a 0-10
VDC proportional voltage output signal on Ana-
log Output #1 of the GBD-X. The GBD-X calcu-
lates and varies this signal depending on the
level of CO

2

in the space as it rises from an ad-

justable minimum setting to an adjustable maxi-
mum level. Also, if desired, Analog Output #2
can provide a 10.0 VDC fixed output signal
whenever the CO

2

is above the minimum set-

point. In addition, Relay Output #1 activates
whenever the CO

2

rises above the minimum set-

point and deactivates when it falls 5 PPM below
the minimum setpoint. Relay Output #2 activates
whenever the CO

2

rises above the maximum

setpoint and deactivates when it falls 5 PPM
below the maximum setpoint.

When more than (6) CO

2

or Temperature Sen-

sors are to be used, a second GBD-X controller
can be connected to the VCM-X and would then
allow the use of from (7) to (12) Room Temperature Sensors or CO

2

Sensor inputs. Each GBD-X controller can be used for

either temperature averaging or CO

2

averaging, but not both on the same GBD-X controller. When both are required at least

(2) GBD-X controllers, one configured for CO

2

control and the other configured for Temperature averaging must be used. Up

to a combined (16) additional GBD-X controllers can be daisy-chained together for a total of (18) GBD-X controllers on one
loop. Either a CommLink or MiniLink PD must always be installed on the controls system when using the GBD-X Controller
due to its broadcast requirements. A personal computer with Prism software installed or the System Manager Touch Screen is
also required to program the GBD-X controller.

Mounting

The GBD-X is provided with an integral plastic enclosure which provides mounting points for mounting inside of a control en-
closure. It is recommended that the GBD-X be mounted in a control enclosure in the building equipment room.

OE332-23-GBDX

GBD-X Controller




Technical Data

OE332-23-GBDX GBD-X Controller

Power

24 Volt AC

Weight

1.5 lb.

Power Consumption

8 VA Maximum

Network Connection

RS-485

Operating Temp

10

F to 149F Protocol

HSI Open Protocol Token Passing

Operating Humidity

90% RH Non-Condensing

Communications

RS-485 - 9600 Baud

Inputs Available

Outputs Available:

Types and Quantity of
User Selectable
Inputs (one of the 3
options at right)

Type III-10kohm input (6)

AO1 Output

0-10 VDC Variable Signal

4-20ma input (6)

AO2 Output

10 VDC Fixed Signal

0-5 VDC (6)

R1 Output

Contact Closure

R2 Output

Contact Closure

Three Year Warranty