MHGRV III Controller Technical Guide

Operator Interface

12

Supply Air Temperature

The DIP switches are only used when the controller is installed as a
stand-alone controller. The main unit controller will set the Supply Air
Temperature Setpoint and Reset Limit when the MHGRV III is used as
an expansion device.

You can set the desired Discharge Air Temperature Setpoint using the DIP
Switch labeled SETPOINT. See Figure 5 for location and DIP Switch
setting instructions. The MHGRV III controller will allow you to set a
Supply Air Temperature Setpoint between 50°F and 100°F. If a value
of less than 50°F is set, the controller will default to a 50°F Supply Air
Temperature Setpoint. A value greater than 100°F will cause the unit to
default to a 100°F Supply Air Temperature Setpoint.

Supply Air Temperature Reset Limit

You can reset the Supply Air Temperature Setpoint by supplying a 0-10
VDC control signal to the Reset Input (RST IN) terminal on the MH-
GRV III controller board. The reset range is determined by the RESET
LIMIT DIP Switch. See Figure 5 for location and setting instructions.
The controller will reset the Supply Air Temperature Setpoint from the

value set on the SETPOINT DIP Switch to the value set on the RESET
LIMIT DIP Switch as the Reset Input (RST IN) signal is increased from
0 Volts to 10 Volts..

Example:
You want the Discharge Air Temperature Setpoint to increase from 55°F
when the Reset Input signal is at 0 Volts and to 75°F when the Reset
Input signal is at 10 Volts.



Set the SETPOINT DIP Switch to 55°F



Set the RESET LIMIT DIP Switch to 75°F

The discharge air temperature will now increase from 55°F to 75°F as
the Reset Input voltage signal ramps from 0 Volts to 10 Volts.

NOTE: It is possible to create a “reverse acting” control sequence.

Using the temperatures from the example above by set-
ting the SETPOINT DIP Switch to 75

F and the RESET

LIMIT DIP Switch to 55

F, the reset would be reverse

acting. In this case, the controller will maintain a 75

F

discharge temperature when the Reset Input signal is at
0 Volts and will reduce it to 55

F when the Reset Input

signal is at 10 Volts.

DIP Switch Settings

DIP Switch Setting Shown

Is For A Setpoint Of 57

DIP Switch Setting Shown

Is For A Setpoint Of 94

ADD

ADD

32 + 16 + 8 + 1 = 57

64 + 16 + 8 + 4 + 2 = 94

All Rocker Switches Depressed

In the Direction Of The ADD Arrow

Are Added Together To Total The Setpoint

Typical DIP Switch

Detail View

F

1

O

F

ADD

4

2

16

8

64

32

128

Figure 5: DIP Switch Setting Instructions