Dip switch settings – Orion System MHGRV III User Manual

Page 13

Advertising
background image

Operator Interface

MHGRV III Controller Technical Guide

13

Field Testing

For fi eld testing purposes, the modulating hot-gas valves can be forced
to full Cooling or full Reheat via DIP switch settings on the MHGRV
III controller. See Table 1 for mode of operation and valve positioning
during force modes.

MHGR Valve - Position & Operation

Setpoint Value

Reset Limit

Value

Mode of

Operation

HGR Valve

Position

1

3

Full Cooling

100% Closed

3

1

Full Reheat

100% Open

3

3

Half Reheat/

Cool

50% Open/

Close

Table 1: MHGR Valve Position & Operation

DIP Switch Settings

NOTE: For a value of 1, only turn on DIP switch labeled 1. For a

value of 3, turn on DIP switches 1 and 2. The DIP switches
are added together to complete a specifi c value.

WARNING: When force mode testing is complete, reset the DIP

switch settings to a valid temperature setting.

Do not leave the MHGRV DIP switches set in force
mode when leaving the job site.

Advertising