Delta Electronics Network Device DOP-A/AE/AS User Manual
Page 104

Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series
Revision January, 2008, Doc. Name: 2007PDD23000007
1-103
CrossReference Table (Inter Memoryof Delta HMI and Modbus Reference Address)
Inter Memory
of Delta HMI
Modbus Reference
Address
Supporting Modbus
Function
Address of Function
$0 40001 03H,
06H,
10H
0000H
$1 40002 03H,
06H,
10H
0001H
.
.
.
$1023 41024
03H,
06H,
10H
03FFH
$M0 42001 03H,
06H,
10H
07D0H
$M1 42002 03H,
06H,
10H
07D1H
.
.
.
$M1023 43024
03H,
06H,
10H 0BCFH
RCPNO 44001
03H,
06H
0FA0H
RCP0 45001
03H,
06H,
10H
1388H
RCP1 45002
03H,
06H,
10H
1389H
.
.
.
$2000.0 00001
01H,
05H,
0FH 0000H
$2000.1 00002
01H,
05H,
0FH 0001H
.
.
.
$2000.15 00016
01H,
05H,
0FH 000FH
$2001.0 00017
01H,
05H,
0FH 0010H
.
.
.
$2063.0 01009
01H,
05H,
0FH 03F0H
.
.
.
$2063.15 01024
01H,
05H,
0FH 03FFH
$M200.0 01025
01H,
05H,
0FH 0400H