Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series

Revision January, 2008, Doc. Name: 2007PDD23000007

1-135

¾

WORD_DEVICE_I / WORD_DEVICE_E / WORD_DEVICE_L / WORD_DEVICE_M: Address must be 1

or the multiple of 16+1.

¾

WORD_DEVICE_X / WORD_DEVICE_Y / WORD_DEVICE_L / WORD_DEVICE_W: Valid address is

inconsecutive.

Contacts

Contact type

Format

Bit No.

BIT_DEVICE_X Xn

n: 201 ~ 65464

BIT_DEVICE_Y Yn

n: 201 ~ 65464

BIT_DEVICE_I In

n: 1 ~ 16384

BIT_DEVICE_E En

n: 1 ~ 4096

BIT_DEVICE_L Ln

n: 1 ~ 65488

BIT_DEVICE_M Mn

n: 1 ~ 9984

BIT_DEVICE_TU

TUn

n: 1 ~ 3072

BIT_DEVICE_CU

CUn

n: 1 ~ 3072

¾

BIT_DEVICE_X / BIT_DEVICE_Y : the last two digits of address must be less than 65 (1 ~ 64).

¾

BIT_DEVICE_X / BIT _DEVICE_Y / BIT _DEVICE_L : valid address is inconsecutive.

¾

Multiple Duplicate:

The next Bit address of X264 is X301 (invalid addresses X265 ~ X300 are skipped)

The next Bit address of X364 is X401.

The address of Y is the same as X.

(The Word addresses of X and Y also skip invalid addresses automatically)

C. Connections (Connector Pinouts)

It needs to use specific cable of YOKOGAWA ACE PLC.

RS-232

DOP

9 pin D-SUB male (RS-232)

Controller (6 pin)

(RS-232 for YOKOGAWA)

Controller (6 pin) (RS-232 for

YOKOGAWA)

RXD (2)

(1) TXD

TXD (3)

GND (5)

(2) RXD

(5) GND

Top View