Fireplace installation – Desa WCM-50J User Manual

Page 7

Advertising
background image

www.desatech.com

122273-01C

7

Note: For outdoor installations, fireplace
enclosure must allow for adequate drainage
and fresh air ventilation. It is recommended
that a sealed, corrosion resistant catch pan
with provision for drainage be installed under
fireplace within fireplace enclosure.

HEARTH ExTENSION

A hearth extension projecting a minimum of
20" in front of and a minimum of 12" beyond
each side of fireplace opening is required to
protect combustible floor construction in front
of fireplace. Fabricate a hearth extension
using a material which meets the following
specifications: a layer of noncombustible,
inorganic material having a thermal conduc-
tivity of K=0.84 BTU IN/FT, HR. F (or less) at
1" thick. For example, if the material selected
has a K factor of 0.25, such as glass fiber, the
following formula would apply:

0.25 x 1.0" = 0.30" thickness required

0.84

Thermal conductivity "K" of materials can be
obtained from manufacturer or supplier of
noncombustible material. If hearth extension
is to be covered, use noncombustible mate-
rial such as tile, slate, brick, concrete, metal,
glass, marble, stone, etc. Provide a means
to prevent hearth extension from shifting and
seal gap between fireplace frame and hearth
extension with a noncombustible material
(see Figure 6).

WARNING: Hearth extension

is to be installed only as shown

in Figure 6.

Fireplace inStallatiOn

Continued

Figure 6 - Hearth Extension

Seal Gap

Fireplace Front

Ember Protector

Fireplace Front
Raised Hearth

Fireplace Front
Elevated

Ember Protector

Ember Protector

Seal Gap

Hearth

Extension

MANTELS

A mantel may be installed if desired (see Figure
7). Woodwork such as wood trims, mantels or
any other combustible material projecting from
front face must not be placed within 12" (36"
Models) or 18" (42/50" Models) of fireplace
opening. Combustible materials above 12" (36"
Models) or 18" (42/50" Models) and projecting
more than 1

1

/

2

" from fireplace must not be

placed less than 15" (36" Models) or 21" (42/50"
Models) from the top opening of the fireplace
(NFPA STD 211, Sec. 7-3.3.3).
Mantels or any other combustible material
also may come up to side edge of black metal
face of fireplace as long as projections from
front face fall within limit shown in Figure 7.

12

1

/

4

" Ref.

6"

Ref.

15" Min. (3

6"

M

od

el

s)

21" Min. (4

2/

50

"

Models)

12" Min.

(36" Models)

18" Min. (42/50"

Models)

1

1

/

2

" Max.

3" Nom.

33°

Combustible
Material

Safe
Zone for
Projection of
Combustible
Materials

Fireplace Opening

Upper

Section of

Fireplace

Figure 7 - Mantel Clearances to

Combustible Material

FIREBOX

SAFE ZONE

Top View of Fireplace

3" Max.

4.5"

Min. to

Perpendicular

Side Wall

7.75" (36" Models)

11.5" (42/50" Models)

33°

Combustible
Material
Must Not
Overlap
Front Face

12" - 36" Models

18" - 42/50" Models