4.4 Serial Port Configuration for DeltaV PSIC

In order for proper communication between the Programmable Serial Interface Card and the
Allen-Bradley PLC, the serial port settings on both devices must be configured properly.

The PSIC serial port can be configured via a combination of the following settings through
the DeltaV Explorer Menu using the Properties box.

· Protocol Type Custom


· Mode

Master


· Retry Count

0 to 255


· Message time-out

100 to 25500ms


· Transmit Delay

0 to 25500ms


· Send Outputs on Startup Yes or No


· Port Type

RS-232, RS-422/485 Half - Duplex, RS -

422/485 Full - Duplex

· Baud Rate

300, 1200, 2400, 4800, 9600, 38400

57600, 115200

· Parity

None, Even or Odd


· Data Bits

7or 8