There are additional switches on the 1785-KE Module (Series B) which may require
adjustment. Refer to the Allen-Bradley User Manual for further information.

· SW1 - RS232C link features


· SW2 - Node number


· SW3 - Data highway Plus and RS-232C communication baud rates, and

Local/Remote option


· SW4 - Reserved for future use.


A.3 1770-KF2 Module Switch Settings

The 1770-KF2 module has 6 switch assemblies which allow the selection of various
communications options. The 1770-KF2 Module RS-232C parameters should be set up
as follows:

· Full duplex


· Same parity as configured for the DeltaV PSIC Port

· BCC error checking


· RS-232 communications baud rate same as DeltaV PSIC Port

· Hardware handshake on

· Duplicate messages - ignore


· Execute diagnostic commands


There are additional switches on the 1770-KF2 module which may require adjustment.
Refer to the Allen-Bradley User Manual for further information.

· SW1 – Configure with parameters as defined above


· SW2/SW3/SW4 – Unique Station number for DH+


· SW5 - Data highway communication baud rate at 57.6k


· SW6 – Computer link baud rate and diagnostic commands

· SW7 – Data Highway +

· SW8 – RS-232


NOTES: Dip switch changes do not take affect until power is cycled on the KF2.
The fourth switch on SW1 must be set to ON. This enables hardware handshaking.