Super Systems AC20 User Manual
Page 43

41
C.I06 -
C.I06 -
C.I06 -
C.I06 -
C.I06 - Set point display type
Set point display type
Set point display type
Set point display type
Set point display type
Upper display: CnF.6
Lower display: SP.dS
Range: Fn.SP = When device is in normal display mode and it is
performing a set point ramp, the middle display
will show the final set point value.
OP.SP= When device is in normal display mode and it is
performing a set point ramp, the middle display
will show the operative set point value.
C.I07 -
C.I07 -
C.I07 -
C.I07 -
C.I07 - Burn Off and Purge activation threshold
Burn Off and Purge activation threshold
Burn Off and Purge activation threshold
Burn Off and Purge activation threshold
Burn Off and Purge activation threshold
Upper display: CnF.6
Lower display: t.t.Ac
Range: the instrument will start the Burn Off and the Purge
procedure according with the following selection:
No = without testing the temperature limit (1000 °F)
YES= if the temperature test is satisfy.
Available::::: When mV is selected as primary control variable.
C.I08 -
C.I08 -
C.I08 -
C.I08 -
C.I08 - Time out selection
Time out selection
Time out selection
Time out selection
Time out selection
Upper display: CnF.6
Lower display: t.out
Range: tñ.10 = 10 s time out
tñ.30 = 30 s time out
CONFIGURATION GROUP [C.Lxx]
CONFIGURATION GROUP [C.Lxx]
CONFIGURATION GROUP [C.Lxx]
CONFIGURATION GROUP [C.Lxx]
CONFIGURATION GROUP [C.Lxx]
INPUT/OUTPUT TEST
This group is displayed only when configuration modify mode is
enabled.
This group allows you to verify the correct working of:
- the relay outputs (OUT 1 up to OUT5),
- digital inputs (diG.1 up to diG.3),
- the inputs from In1 up to In8 and the relays of the outputs from
OUT10 up to OUT19, if the optional I/O card is fitted.
When an output is in "On" status, the related LED will light up
(for OUT 5 is used the "ST" LED)
C.L01 OUT 1 status
C.L01 OUT 1 status
C.L01 OUT 1 status
C.L01 OUT 1 status
C.L01 OUT 1 status
Upper display: VErF
Lower display: OU.1
Range: On
= Output enabled (relay energized)
OFF
= Output disabled (relay deenergized)