Super Systems eFLO User Manual

Page 22

Advertising
background image

eFlo Electronic Flow Meter Operations Manual

Super Systems Inc.

Page 22 of 25

Problem

Possible Causes

Possible Corrective Actions

Unit is indicating that there is no gas flow when

calling for a flow setpoint

Hand valve for gas supply may be closed

If a solenoid is used, solenoid may not be

energized

Restrictions may be present downstream in the

gas supply

Open hand valve.

Ensure that solenoid is energized.

Check for issues such as exhaust gas outlet

restriction, and correct any problems.

Unit is not communicating

Communications may not be configured correctly Verify RS485 wire polarity

Verify address and baud rate

Verify that only one meter has address set to 1 on

the RS485 loop

Unit is not reaching setpoint

There may be insufficient gain

Verify gain is high enough; adjust bias as needed

Setpoint cannot be changed directly from the

eFlo control panel

An analog setpoint signal may be wired and

overwriting manual setpoint

A master device wired to the eFlo may be

overwriting manual setpoint

Ensure that an analog input signal to the eFlo is

not wired and overwriting manual setpoint

Ensure that no device is actively writing the

setpoint via communications

Table 5 - Troubleshooting

If you experience problems and cannot find the solution after troubleshooting, please call SSi Technical Support at (513) 772-0060.

Advertising