6 relay output wiring – Tecfluid MT03F User Manual
Page 11

11
3.2.6 Relay
output
wiring
Terminal
Description
Relay
13
Normally open
Relay 1
14
Normally closed
Relay 1
15
Common
Relay 1
16
Normally open
Relay 2
17
Normally closed
Relay 2
18
Common
Relay 2
The relay outputs provide relays with potential free contacts (see characteristics on page
37).
The status of the relay contacts corresponds to the relay at rest
.
The relay contacts are not protected in any way, and therefore they must be installed
externally
as required in the application
, taking into account the limitations of the
characteristics of such contacts.
In the case of having inductive loads, and to extend the working life of the relay contacts,
it is recommended to use overvoltage protection (VDR for AC and diodes for DC loads).
In all cases a fuse or some kind of protection against short circuits
should always be
provided
according to the needs of the intended load.