Tri Tool 765RVC Hyrdaulic Power Supply User Manual
Page 27

27
Model 765 RVC Hydraulic Power Supply
92-0306 : Rev. 140715
Ensure that the connections are solid and the nuts and bolts and well
insulated.
At least four layers of electrical tape must cover the wire ends and connecting
bolts.
The field winding ends are located in the small box on the side of the motor.
Overload Relay
The overload relay is mounted directly to the magnetic starter in the control
box.
The relay or circuit breaker provides over heat protection by killing the motor if
it starts to draw excessive amperage.
Install a 40-ampere range relay for 240 VAC Three (3) Phase Power and set
the variable amperage slide switch to 40 amps (P/N 70-0111).
Install a 20-ampere range relay (P/N 70-0690) for 460 VAC, Three (3) Phase
power and set the amperage to 20 amps.