Chapter 4 Parameters|

Revision May 2008, ME14, SW V3.04

4-73

Pr.97

Preset Count Down Completion

Settings 00 to 9999

Factory Setting: 00

This parameter sets a preliminary count value for the internal counter. Counter is incremented

by a low-to-high transition on one of the programmed Multi-Function Input Terminals: M1 or

M2 (see Pr.44 or Pr.45, setting 14). Count starts at 01. Upon completion the selected Multi-

Function Output Terminal will close. Preliminary Count could be used to initiate an external

event before the “terminal count” is reached. (See Pr.38, 39, 40, 41, 42, 45, and 46 for further

details.)

Pr.98

Total Time Count from Power On (Days)

Settings 00 to 65535 days

Read Only

Pr.99

Total Time Count from Power On (Minutes)

Settings 00 to 1440 minutes

Read Only

Pr.100

Software Version

Read Only

This parameter shows the software version for the AC motor drive.

Pr.101

Auto Acceleration/Deceleration

Factory Setting: 00

Settings

00

Linear

acceleration/deceleration

01 Auto acceleration, linear deceleration

02 Linear acceleration, auto deceleration

03

Auto

acceleration/deceleration

04 Linear Accel/Decel Stall Prevention during Deceleration

(Please refer to Accel/Decel time setting at parameter Pr.10-Pr.13)

When this parameter is set to 03, the AC drive will accel/decel in the fastest and smoothest

possible way by automatically adjusting the accel /decel time.

This parameter provides five modes to choose:

00

Linear acceleration and deceleration (operation by Pr.10, Pr.11, or Pr.12, Pr.13

acceleration/deceleration time)

01

Automatic acceleration, linear deceleration (Operation by automatic acceleration,

Pr.11 or Pr.13 deceleration time).