Chapter 4 Parameters|

Revision May 2008, ME14, SW V3.04

4-29

Pr.29

DC Braking Time during Start-up

Unit: 0.1sec

Settings 0.0 to 5.0 sec

Factory Setting: 0.0

This parameter determines the duration for the DC Braking Current applied during starting. DC

Braking is applied until the Minimum Frequency is reached.

Pr.30

DC Braking Time during Stopping

Unit: 0.1sec

Settings 0.0 to 25.0 sec

Factory Setting: 0.0

This parameter determines the duration for the DC Braking voltage to be applied during

stopping. If stopping with DC Braking is desired, then Pr.02 must be set to Ramp to Stop (0.0).

Pr.31

Start-Point for DC Braking

Unit: 0.1sec

Settings 0.00 to 60.00Hz

Factory Setting: 0.00

This parameter sets the frequency at which the DC Braking will begin during deceleration.

Master
Frequency

Min. output
Freq.

Pr.29

Pr.31

Pr.30

DC Braking Current %

ON

OFF

Pr.28

Start-point

for DC

braking

Operation
command

time(s)

Notes:

1. DC Braking during starting is used for loads that may move before the AC drive starts, such

as hoists and cranes. These loads may also be moving in the wrong direction. Under such

circumstances, the DC Braking can be used to hold the load in position before applying a

forward motion.

2. DC Braking during stopping is used to stop faster than the ramp-to-stop or to hold a

stopped load in position. A dynamic brake resistor may be needed in order to stop loads of

high inertia.