Chapter 4 Parameters|

Revision May 2008, ME14, SW V3.04

4-11

Parameter

Explanation

Settings

Factory

Setting

Customer

Pr.110

Voltage of Zero Speed
Control

0.0 to 20.0 % of Max. output voltage (Pr.05)

5.0

Pr.111

Decel S-curve

00 to 07

00

Pr.112

External Terminal
Scanning Time

01 to 20

01

Pr.113

Restart Method after
Fault (oc, ov, BB)

00: None speed search
01: Continue operation after fault speed

search from speed reference

02: Continue operation after fault speed

search from Minimum speed

01

Pr.114

Cooling Fan Control

00: Fan Off when the drive stop after 1 Min.
01: AC Drive Runs and Fan On, AC Drive

Stops and Fan Off

02: Always Run
03: Reserved

02

Pr.115

PID Set Point
Selection

00: Disable
01: Keypad (based on Pr.00 setting)
02: AVI (external 0-10V)
03: ACI (external 4-20mA)
04: PID set point (Pr.125)

00

Pr.116

PID Feedback
Terminal Selection

00: Input positive PID feedback, PV from AVI

(0 to 10V)

01: Input negative PID feedback, PV from

AVI (0 to 10V)

02: Input positive PID feedback, PV from

ACI (4 to 20mA)

03: Input negative PID feedback, PV from

ACI (4 to 20mA)

00

Pr.117

Proportional Gain (P) 0.0 to 10.0

1.0

Pr.118

Integral Time (I)

0.00: Disable
0.01 to 100.0 sec

1.00

Pr.119

Differential Time (D)

0.00 to 1.00 sec

0.00

Pr.120

Integration’s Upper
Bound Frequency

00 to 100 %

100 %

Pr.121

One-Time Delay

0.0 to 2.5 sec

0.0

Pr.122

PID Frequency Output
Command Limit

00 to 110 %

100

Pr.123

Feedback Signal
Detection Time

0.0: Disable
0.1 to 3600 sec

60.0

Pr.124

Feedback Signal Fault
Treatment

00: Warning and RAMP to stop
01: Warning and keep operating

00