Verilink 1200 Rack Pwr Spply (IG) Configuration/Installation Guide User Manual

1200 rmps, Rack mount power supply), Specifications

Advertising
background image

T

R

A

N

S

P

O

R

T

®

1200 RMPS

(Rack Mount Power Supply)

Part Number 45- 00032

Rev 2.0

T

R

A

N

S

P

O

R

T

®

The TxPORT 1200 RMPS installs in a standard 19" rack. When inserting the unit, install the bottom two screws in the mounting brackets first.
This will prevent the weight of the unit from potentially bending the mounting brackets. The 1200 RMPS weighs up to 60 pounds. Use
extreme caution when installing the unit in the rack to avoid possible personal injury and/or damage to other equipment.

AC power is acquired through an industry standard 110 V power cord (supplied).

The alarm contacts on the ALARM barrier strip (rear panel) are labeled COM (common), NC (normally closed), and NO (normally open). The
alarm may be cut off with the ALARM CUT OFF switch (front panel).

The 1200 contains no user-serviceable parts or field options. If servicing or power optioning (24/48 VDC) is required, return the unit t o
T x P O RT C u s t o m e r S e r v i c e .

Fused Outputs:

16 individual fused outputs (3 amps, GMT type)

Overload Protection: Current limited, constant voltage transformer

Input Fuse:

6.3 amps

Input Connectors:

Industry standard AC male connector

Output Connectors:

Screw terminal, 16 position

LED Indicators:

Power ON/OFF, Fuse Alarm, Alarm Cut-off

Isolation Rating:

Class 130, UL 1446

POWER

Current:

48 VDC, 5 amps redundant or 10 amps non-redundant

24 VDC, 10 amps redundant or 20 amps non-redundant

AC Input:

100 -130 VAC, 60 Hz, 6 amps (maximum)

Power Input:

300 watts (maximum)

Heat Generation:

204 BTU

Efficiency:

80%

MECHANICAL

Dimensions:

16" W, 5" H, 12" D

Weight:

60 lbs. (maximum)

Cooling:

Forced air

ENVIRONMENTAL

Operating Temp:

0° to 60° C (32° to 140°F)

Storage Temp:

-20° to 80° C (- 4° to 176°F)

Humidity:

95% maximum, non - condensing

NEBS Zone 4:

Certified

-48 VDC

9 10111213141516

-48 VDC

1 2 3 4 5 6 7 8

RTN

1 2 3 4 5 6 7 8

RTN

9 10111213141516

ALARM

COM NC NO

MODEL NO.

SERIAL NO.

I

O

FUSE

Rear Panel

Front Panel

SPECIFICATIONS

1200 RMPS

ALARM

ALARM

CUT OFF

POWER

1

Fused Output

2 3 4 5 6 7 8

9 10111213141516

Fused Output

Advertising