Verilink 1557 (CG) Configuration/Installation Guide User Manual

Page 3

Advertising
background image

1
5
5
8

— CONFIGURATION NOTES —

• TAPS units must be configured in pairs. In each

pair, one unit must be configured as a MASTER
and one as a SLAVE.

• Each pair of TAPS units must be configured for

the same mode, NORMAL or TRANSPARENT

• A pair of TAPS units configured as NORMAL

may not be placed in the same circuit with a pair
configured as TRANSPARENT.

• It is allowed (as the diagram shows) to have two

pairs of TAPS units on the same circuit if they are
configured for NORMAL mode.

• Take note of the setting for switches S2-7 and S2-

8. These switches determine the CONFIGURA-
TION SOURCE for the 1557 card. Switch
options for Configuration Source are shown on
the front page of this document. The four choices
are explained in the 1557 Users Manual.

• A 1559 APS Manager connected to a 1557 con-

figured as a MASTER unit can monitor and do
maintenance functions on both the master unit
and its corresponding slave unit.

• A 1559 APS Manager connected to a 1557 con-

figured as a SLAVE unit can monitor only the
performance data for the slave unit. No mainte-
nance functions are available through the slave
unit.

Normal Slave

Transparent Slave

Transparent Master

Normal Master

CO #1

CO #2

CO #2

CO #1

1
5
5
7

1
5
5
7

1
5
5
8

CPE

CPE

A

B

IOC

EQUIPMENT

EQUIPMENT

ACCESS

S2-5 closed

1 2 3 4 5 6 7 8

OPEN

S3-6 open

1 2 3 4 5 6 7 8

OPEN

S2-5 closed

1 2 3 4 5 6 7 8

OPEN

S3-6 closed

1 2 3 4 5 6 7 8

OPEN

S2-5 open

1 2 3 4 5 6 7 8

OPEN

S3-6 open

1 2 3 4 5 6 7 8

OPEN

S2-5 open

1 2 3 4 5 6 7 8

OPEN

S3-6 closed

1 2 3 4 5 6 7 8

OPEN

CPE

ACCESS

A

B

EQUIPMENT

EQUIPMENT

ACCESS

CPE

IOC

B

A

1
5
5
7

1
5
5
7

Advertising