WCC III Technical Guide

15-4

15. SAT 3C/D/F INSTALLATION

Typical WCC III Installation

The SAT 3C controller is used to interface to dedicated Roof Top controller units (RTU-17 type controllers) and other
more specialized controllers (GPC type devices). Each one of the SAT 3C controllers takes up 8 Satellite addresses and
then can communicate with up to 8 special dedicated controllers. Electrically, this SAT 3C device only takes up "ONE"
satellite load. There may be up to 60 satellite loads per WCC3 satellite communications loop. An optional additional
WCC3 M-COMM loop EXP board is available that will provide an additional two WCC3 satellite communications
loops if needed.

The SAT 3P controller is used to measure up to 8 dry contact closures from up to 8 pulse meters, such as a Emon-Dmon
KWH meters. (Please note: Each SAT III controller can also interface to a single dry contact closure from a single pulse
meter on A1 input.) This SAT 3P controller is a stripped down SAT III controller with only 8 pulse type inputs. Besides
logging abilities, there are not any other functioning satellite features in this SAT 3P controller. Each one of the SAT 3P
controllers takes up 8 Satellite addresses. Electrically, this SAT 3P device only takes up "ONE" satellite load. There may
be up to 60 satellite loads per WCC3 satellite communications loop. An optional additional WCC3 M-COMM loop
EXP board is available that will provide an additional two WCC3 satellite communications loops if needed.

The WCC II to WCC III global bridge is a device that allows for data from the "old" WCC II system to be shared with a

"new" WCC III system. It was designed as a temporary solution while the WCC II system was being changed over to a

WCC III system. Electrically, this WCC II to WCC III Global Bridge device only takes up "ONE" satellite load. There
may be up to 60 satellite loads per WCC3 satellite communications loop. An optional additional WCC3 M-COMM
loop EXP board is available that will provide an additional two WCC3 satellite communications loops if needed.

The high speed cable \DSL modem is used to connect the WCC III - MCD to the internet. Alternate connections to the
internet, or even the building intranet is possible, but they will require additional IT support at the contractor level.

Typical WCC III System Installation - Multiple buildings with fiber optics connecting the two buildings. Also
shown with the use of Power and Switchable comm boards.

OE210
TYPICAL
SPACE
SENSOR
(X8 MAX)

ON/OFF RELAY
PUMPS, LIGHTS,
ETC.

8

7

SAT ADDRESS

2
1

4

8

WattMaster Controls Inc.

BINARY
INPUTS

BINARY

INPUTS

L8

ON OFF

128

32
16

64

L4
L3
L2
L1

L6
L5

L7

L11

L12

ON OFF

L10
L9

ON OFF

L15

L16

L14
L13

C

H

4

3

5
6

2

1

LOCAL SET

STATUS 2

STATUS 3

STATUS 1

HSS XMIT

LOCAL SET

LOCAL SET DISABLE

BATT ON/ OFF
PULSE INPUT

OPTION 1

TEST

OPTION 3
OPTION 2

ON OFF

STATUS

HSS REC

SAT XMIT

SAT REC

ANALOG INPUT

JUMPER SELECTION

CURRENT
INPUT

THERMISTOR
INPUT

0 TO 10V
INPUT

0 TO 5V
INPUT

0 TO 1V
INPUT

PROGRAMMABLE CONTROLLER

SAT III

H

C

COM

CHANNEL

2

1

3

4

2

1

3

4

5

6 7 8

5

6 7 8

V

OUT

GND

L
O
A
D

+V

ATI

8

7

SAT ADDRESS

2
1

4

8

WattMaster Controls Inc.

BINARY
INPUTS

BINARY

INPUTS

L8

ON OFF

128

32
16

64

L4
L3
L2
L1

L6
L5

L7

L11

L12

ON OFF

L10
L9

ON OFF

L15

L16

L14
L13

C

H

4

3

5
6

2

1

LOCAL SET

STATUS 2

STATUS 3

STATUS 1

HSS XMIT

LOCAL SET

LOCAL SET DISABLE

BATT ON/ OFF
PULSE INPUT

OPTION 1

TEST

OPTION 3
OPTION 2

ON OFF

STATUS

HSS REC

SAT XMIT

SAT REC

ANALOG INPUT

JUMPER SELECTION

CURRENT
INPUT

THERMISTOR
INPUT

0 TO 10V
INPUT

0 TO 5V
INPUT

0 TO 1V
INPUT

PROGRAMMABLE CONTROLLER

SAT III

H

C

COM

CHANNEL

2

1

3 4

2

1

3

4

5

6 7 8

5

6 7 8

V

OUT

GND

L
O
A
D

+V

ATI

"D" MODE

"C" MODE

"C" MODE ADDRESSING NOTES
"C" MODE SAT III ADDRESSING STARTS
AT ADDRESS 8.

EACH "C" MODE SAT III TAKES UP
8 SAT III LOGICAL ADDRESSES.

A "C" MODE SATIII CAN COMMUNICATE
WITH 8 DEVICES TOTAL.

"D" MODE ADDRESSING NOTES
"D" MODE SAT III ADDRESSING STARTS

AT ADDRESS 4.
EACH "D" MODE SAT III TAKES UP 4

SAT III LOGICAL ADDRESSES.
A "D" MODE SAT III CAN COMMUNICATE

WITH 32 DEVICES TOTAL.

SAT IIICD

Communications Interface

TUC XMIT

ON OFF

ON OFF

SAT ADDRESS

1

STATUS

LOCAL SET

16

4
2

8

64
32

128

LOCAL SET DISABLE

OPTION 2

LOCAL SET

OPTION 1

TEST

BATT ON/ OFF

TUC REC

SAT XMIT

SAT REC

OE320

TUC-2R

OE331

TUC-5R+

W
A
R
M
E
R

C
O
O
L
E
R

OVR

OE213
TYPICAL
SPACE
SENSOR

OE421- SAT III
CONTROLLER

OE454/O 455/OE456

E

SAT 3C/D/F

CONTROLLER

W
A
R
M
E
R

C
O
O
L
E
R

OVR

OE213
TYPICAL
SPACE
SENSOR

WCC II TO WCC III
GLOBAL BRIDGE

WCC III-MCD

SINGLE PULSE
INPUT FROM
POWER METER

UP TO 32 TOTAL
FAN COIL, HEAT PUMP
PD VAV TERMINAL UNITS
PI VAV TERMINAL UNITS
PARALLEL FAN BOX, ETC.

VAV BOX

16 OUTPUTS

PER SAT III

UP TO 60 TOTAL SAT III
OR SAT 3C/D/F/P PER LOOP.
THERE ARE 4 POSSIBLE

SAT III RS485
COMMUNICATIONS LOOPS
(UP TO 239 SAT III MAXIMUM)

TO THE ISP
(INTERNET SERVICE PROVIDER)
CONNECTION TO THE INTERNET
(BY OTHERS)

HIGH SPEED CABLE
MODEM / ROUTER

ETHERNET
CABLE

Optional V-OUT Board

( 8 RELAY OUTS)

(2 PER SAT III)

Optional B-INPUT Board

( 8 BINARY INPUTS)

(2 PER SAT III)

HSS PORT

HEAT PUMP

SAT II

SAT III

PROGRAM SOCKET

ADDRESS

24C128

PCF8583

LT1785

WATTMASTER CONTROLS INC

CONNECTION
TO OLD WCC II
MANCHESTER
COMM LOOP

1

2
4
8

16
32
64

128

ADDRESS

SATIII-P

TEST

LOCAL
L DIS

OPT 1
OPT 2
OPT 3

R

T

24 VAC

GND

OPTIONS

PULSE INPUTS

“P” MODE ADDRESSING NOTES

SAT III ADDRESSING STARTSAT

ADDRESS NUMBER 8.

EACH "P" MODE SAT III TAKES UP

(8) SAT III LOGICAL ADDRESSES.

THERE ARE ONLY (8) USED ACTIVE

INPUTS PER SAT 3P.

ANALOG INPUT #1 (PULSE INPUT #1)

ON EACH SAT III ADDRESS IS ACTIVE.

ALL OTHER INPUTS AND OUTPUTS ON

THE SAT 3P ARE NOT FUNCTIONAL.

TOTAL WIRING FOR EACH INPUT NOT

TO EXCEED 100 FEET.

USE 18 GAUGE TWISTED PAIR WITH

SHIELD FOR EACH PULSE METER

CONNECTION.

CONNECT THE SHIELD WIRE TO GND.

HSS PORT

MULTIPLE PULSE
INPUTS FROM
POWER METERS

OE455-P
SAT 3P
CONTROLLER

PL102224
POWER AND
SWITCHABLE COMM

USUALLY ONE
OR TWO PER
FLOOR

SAT COMM LOOP

SAT COMM LOOP

SAT COMM LOOP

TUC COMM LOOP

B B

PL102224
POWER AND
SWITCHABLE COMM

USUALLY ONE
OR TWO PER
FLOOR

FIBER OPTIC LINES
MAXIMUM OF 2.5 MILES
(USES "ST" CONNECTORS)

BUILDING # 2

8

7

SAT ADDRESS

2
1

4

8

WattMaster Controls Inc.

BINARY
INPUTS

BINARY
INPUTS

L8

ON OFF

128

32
16

64

L4
L3
L2
L1

L6
L5

L7

L11

L12

ON OFF

L10
L9

ON OFF

L15

L16

L14
L13

C

H

4

3

5
6

2

1

LOCAL SET

STATUS 2

STATUS 3

STATUS 1

HSS XMIT

LOCAL SET

LOCAL SET DISABLE

BATT ON/ OFF
PULSE INPUT

OPTION 1

TEST

OPTION 3
OPTION 2

ON OFF

STATUS

HSS REC

SAT XMIT

SAT REC

ANALOG INPUT

JUMPER SELECTION

CURRENT
INPUT

THERMISTOR
INPUT

0 TO 10V
INPUT

0 TO 5V
INPUT

0 TO 1V
INPUT

PROGRAMMABLE CONTROLLER

SAT III

H

C

COM

CHANNEL

2

1

3

4

2

1

3

4

5

6 7 8

5

6 7 8

V

OUT

GND

L
O
A
D

+V

ATI

OE421- SAT III
CONTROLLER

8

7

SAT ADDRESS

2
1

4

8

WattMaster Controls Inc.

BINARY
INPUTS

BINARY
INPUTS

L8

ON OFF

128

32
16

64

L4
L3
L2
L1

L6
L5

L7

L11

L12

ON OFF

L10
L9

ON OFF

L15

L16

L14
L13

C

H

4

3

5
6

2

1

LOCAL SET

STATUS 2

STATUS 3

STATUS 1

HSS XMIT

LOCAL SET

LOCAL SET DISABLE

BATT ON/ OFF
PULSE INPUT

OPTION 1

TEST

OPTION 3
OPTION 2

ON OFF

STATUS

HSS REC

SAT XMIT

SAT REC

ANALOG INPUT

JUMPER SELECTION

CURRENT
INPUT

THERMISTOR
INPUT

0 TO 10V
INPUT

0 TO 5V
INPUT

0 TO 1V
INPUT

PROGRAMMABLE CONTROLLER

SAT III

H

C

COM

CHANNEL

2

1

3 4

2

1

3

4

5

6 7 8

5

6 7 8

V

OUT

GND

L
O
A
D

+V

ATI

OE421- SAT III
CONTROLLER

"D" MODE

"C" MODE

"C" MODE ADDRESSING NOTES
"C" MODE SAT III ADDRESSING STARTS

AT ADDRESS 8.
EACH "C" MODE SAT III TAKES UP

8 SAT III LOGICAL ADDRESSES.
A "C" MODE SATIII CAN COMMUNICATE

WITH 8 DEVICES TOTAL.

"D" MODE ADDRESSING NOTES
"D" MODE SAT III ADDRESSING STARTS
AT ADDRESS 4.

EACH "D" MODE SAT III TAKES UP 4
SAT III LOGICAL ADDRESSES.

A "D" MODE SAT III CAN COMMUNICATE
WITH 32 DEVICES TOTAL.

SAT IIICD

Communications Interface

TUC XMIT

ON OFF

ON OFF

SAT ADDRESS

1

STATUS

LOCAL SET

16

4
2

8

64
32

128

LOCAL SET DISABLE

OPTION 2

LOCAL SET

OPTION 1

TEST

BATT ON/ OFF

TUC REC

SAT XMIT

SAT REC

OE320

TUC-2R

W
A
R
M
E
R

C
O
O
L
E
R

OVR

OE213
TYPICAL
SPACE
SENSOR

OE455

SAT 3D

CONTROLLER

VAV BOX

PL102335
RS-485 TO FIBER
OPTIC ADAPTER

USED IN MULTIPLES
OF TWO

PL102335
RS-485 TO FIBER
OPTIC ADAPTER

SAT COMM LOOP

SAT COMM LOOP

SAT COMM LOOP

UP TO 32 TOTAL
FAN COIL, HEAT PUMP
PD VAV TERMINAL UNITS
PI VAV TERMINAL UNITS
PARALLEL FAN BOX, ETC.

TUC COMM LOOP

OPTION 4
OPTION 3

OPTION 4
OPTION 3