18. SAT 3P INSTALLATION GUIDE

When sharing a common transformer to power other Satellite
Controllers, the transformer used for powering multiple SAT III,
SAT 3C, SAT 3D, SAT 3F, or SAT 3P controllers needs to be of the
self fusing type, or the transformer needs to have an appropriately
sized fuse on the secondary side of the transformer (on the 24VAC
side). VA ratings for the various Satellites that are connected to the
satellite controllers must be accounted for and must be added up,
and an appropriate sized transformer must be used, along with an
appropriate sized fuse on the secondary side of the transformer that
must also be used. All wiring is to be done in accordance with all
national, state, and local electrical codes.

8

7

SAT ADDRESS

2

1

4

8

A 3 WIRE ROOM SENSOR WILL NOT
REQUIRE A LOAD RESISTOR WHEN SET
FOR A 1 VOLT INPUT.

WattMaster Controls Inc.

BINARY
INPUTS

BINARY
INPUTS

L8

ON OFF

128

32

16

64

L4

L3

L2

L1

L6

L5

L7

L11

L12

ON OFF

L10
L9

ON OFF

L15

L16

L14

L13

C

H

4

3

5
6

2

1

LOCAL SET

STATUS 2

STATUS 3

STATUS 1

HSS XMIT

LOCAL SET

LOCAL SET DISABLE

BATT ON/ OFF

PULSE INPUT

OPTION 1

TEST

OPTION 3

OPTION 2

ON OFF

STATUS

HSS REC

SAT XMIT

SAT REC

ANALOG INPUT

JUMPER SELECTION

A 2 WIRE ROOM SENSOR WILL REQUIRE
A 300 OHM LOAD RESISTOR WHEN SET
FOR A 1 VOLT INPUT.

A 4 TO 20 mA SENSOR WILL REQUIRE A
50 OHM LOAD RESISTOR WHEN SET FOR
A 1 VOLT INPUT, OR A 250 OHM LOAD
RESISTOR WHEN SET FOR A 5 VOLT INPUT.

CURRENT
INPUT

THERMISTOR
INPUT

0 - 1V

0 - 5V

0 - 10V

THERM

0 - 1V

0 - 5V

0 - 10V

THERM

0 TO 10V
INPUT

0 TO 5V
INPUT

0 TO 1V
INPUT

0 - 10V

0 - 1V

0 - 5V

0 - 10V

THERM

0 - 1V

0 - 5V

THERM

0 - 1V

0 - 5V

0 - 10V

THERM

PROGRAMMABLE CONTROLLER

SAT III

EACH CONTACT
IS RATED FOR
24VAC OR VDC
@ .5 AMP MAX

0-15VDC
OUTPUT

MIN LOAD
IS 1K OHM
RESISTIVE
VDC ONLY

TO HSS EXPANSION BOARDS.
UP TO TWO BINARY INPUT
BOARDS, AND UP TO TWO
BINARY OUTPUT BOARDS
MAY BE CONNECTED TO A
SAT III CONTROLLER.

SAT III CONTROLLER

24VAC
FUSED

24VA

C

GND

GROUND

WARNING:

OBSERVE POLARITY

BETWEEN THE SAT III CONTROLLER
AND THE SAT 3P CONTROLLER -
GROUND CONNECTIONS MUST BE THE
SAME.

TO OTHER
SAT III OR TO
WCC III - MCD

24VAC

120VAC

PULSE 1
PULSE 2
PULSE 3
PULSE 4
PULSE 5
PULSE 6
PULSE 7
PULSE 8
STAT REC
STAT XMIT
LOCAL SET
STATUS

COMM

ADD

1

2

4

8

16

32

64

128

ADDRESS

SATIII-P

PULSE METER BOARD

ATTMASTER CONTROLS

YS102268 REV0

MADE IN USA

P1

P2

P3

P4

P5

P6

P7

P8

GND

GND

POWER

SEL

TEST

LOCAL

L DIS

OPT 1

OPT 2

OPT 3

SH

R

T

24 VAC

GND

OPTIONS

PULSE INPUTS

“P” MODE ADDRESSING NOTES

SAT III ADDRESSING STARTSAT

ADDRESS NUMBER 8.

EACH "P" MODE SAT III TAKES UP

(8) SAT III LOGICAL ADDRESSES.

THERE ARE ONLY (8) USED ACTIVE

INPUTS PER SAT 3P.

ANALOG INPUT #1 (PULSE INPUT #1)

ON EACH SAT III ADDRESS IS ACTIVE.

ALL OTHER INPUTS AND OUTPUTS ON

THE SAT 3P ARE NOT FUNCTIONAL.

TOTAL WIRING FOR EACH INPUT NOT

TO EXCEED 100 FEET.

USE 18 GAUGE TWISTED PAIR WITH

SHIELD FOR EACH PULSE METER

CONNECTION.

CONNECT THE SHIELD WIRE TO GND.

SAT 3P Typical Wiring Diagram

Use the following Pulse Meter
E-Mon D-Mon Series 2000 with P2 Pulser Output Module option.
Times eight Pulse Meters.

KW

METER

KW

METER

KW

METER

KW

METER

KW

METER

KW

METER

KW

METER

KW

METER

SAT 3P

CONTROLLER

WARNING:

OBSERVE POLARITY

BETWEEN THE SAT 3P CONTROLLER
AND THE SAT III CONTROLLER -
GROUND CONNECTIONS MUST BE THE

SAME.

120VAC WIRING IS BY OTHERS
THE VA RATING FOR THE SAT III IS 15VA.
THE VA RATING FOR THE SAT 3C IS 10VA.
THE VA RATING FOR THE SAT 3D IS 10VA.
THE VA RATING FOR THE SAT 3P IS 3 VA.

TO OTHER SAT III CONTROLLERS, OR
SAT 3C CONTROLLERS, OR SAT 3D
CONTROLLERS, OR SAT 3F CONTROLLERS,
OR SAT 3P CONTROLLERS,
OR TO THE WCC III - MCD COMPUTER
WIRE "R" TO "R", "T" TO "T", "SHLD" TO "SHLD"

KW

METER

SAT III Typical Wiring Diagram

Use the following Pulse Meter
E-Mon D-Mon Series 2000 with the P2 Pulser
Output Module option
Can only connect One Pulse Meter per SAT III.

SAT III Ain #1 jumper set for 0-5V input,

Vout #1 output voltage programmed for
constant 5 volt output. PULSE INPUT switch

"ON".

(+)

(-)

(-)

(+)

(-)

(+)

(-)

(+)

(-)

(+)

(-)

(+)

(-)

(+)

(-)

(+)

(-)

(+)

Figure 18-5: SAT 3P Controller Typical Wiring Diagram

The transformer used for powering the SAT 3P controller needs to
be of the self fusing type or it needs to have an appropriately sized
fuse on the secondary side of the transformer (24VAC Side).

SAT 3P Typical Wiring