Westermo ODW-730-F1 User Manual

Page 17

Advertising
background image

17

6651-2241

… Make sure that DIP-switches S1:8 and S2:2 – S2:8 are set to factory default positions.

(I.e. S1:8 OFF, S2:2 OFF, S2:3 ON and S":4 – S2:8 OFF).

… Configure both ODW-730-F1 units for the correct speed and data format using DIP-

switches S1:1 – S1:7.

… Select RS-485 2- or 4-wire mode using DIP-switch S2:1 (OFF = 2-wire, ON = 4-wire).

… Enable the RS-485 termination / fail safe if required using DIP-switches S3:1 – S3:4

(S3:1 asnd S3:2 = 4-wire termination, S3:3 and S3:4 = 2-wire connection.)

… Connect the fibre link between the ODW-730-F1.

… Connect the power supply to both ODW-730-F1.

… After a few seconds the fibre link should be in operation, indicated by an active CH1

LED.

… Connect the serial cables from PLC master and slave to respective ODW-730-F1.

… Frames from PLC master that are correctly received in the ODW-730-F1 will be

indicated by flashing TD LED.

… Frames that are received via the fibre link will be transmitted to the PLC slave

and indicated by flashing RD LED.

… Replies from slave to master will be transferred and indicated in the opposite way.

… The point-to-point application is up and running.

POWER

CH 1

COM +VA +VB COM

POWER

CH 1

COM +VA +VB COM

TX

RX

TX

RX

Start up guide, point-to-point application
Follow the steps below to get the unit up and running in a simple application.

Master

Slave

Advertising
This manual is related to the following products: