Switch settings ld-64, Turning time/data rate/ connected units, Selection of 2- or 4-wire – Westermo LD-64 User Manual

Page 17: Selection of master/slave, Selection of bits

Advertising
background image

17

6073-2002

Turning Time/Data rate/

Connected units

S1

ON

1 2 3 4 5 6 7 8 9

S1

ON

1 2 3 4 5 6 7 8 9

S1

ON

1 2 3 4 5 6 7 8 9

S1

ON

1 2 3 4 5 6 7 8 9

S1

ON

1 2 3 4 5 6 7 8 9

S1

ON

1 2 3 4 5 6 7 8 9

S1

ON

1 2 3 4 5 6 7 8 9

S1

ON

1 2 3 4 5 6 7 8 9

S1

ON

1 2 3 4 5 6 7 8 9

S1

ON

1 2 3 4 5 6 7 8 9

20

Number**

of units

20

20

20

20

20

20

15

10

5

Selection of 2- or 4-wire

4-wire

S1

ON

1 2 3 4 5 6 7 8 9

2-wire

S1

ON

1 2 3 4 5 6 7 8 9

Selection of Master/Slave

Slave

S1

ON

1 2 3 4 5 6 7 8 9

Master

S1

ON

1 2 3 4 5 6 7 8 9

Selection of bits

9

S1

ON

1 2 3 4 5 6 7 8 9

10

S1

ON

1 2 3 4 5 6 7 8 9

11

S1

ON

1 2 3 4 5 6 7 8 9

*

S1

ON

1 2 3 4 5 6 7 8 9

Selection of 2-wire RS-485 or 4-wire RS-422.
For RS-232 S1:1 can be ignored.

Switch settings LD-64

0.4 ms

2 400 bit/s

Turning-

time

Transmission*

rate

0.2 ms

4 800 bit/s

0.1 ms

9 600 bit/s

50 µs

19 200 bit/s

25 µs

38 400 bit/s

16 µs

62 500 bit/s

11 µs

93 750 bit/s

9 µs

115.2 kbit/s

6 µs

187.5 kbit/s

3 µs

375 kbit/s

* Use this setting for synchronous or other

asynchronous protocols.
The transmitter will be active from the
startbit to 10 bit-times after the last high
databit (see example below). The speed
shall be set to

≅

10 times the required

communication speed.

Please note that only one master can be
used per system.

Start bit

1 bit = 52µs

1 bit: 1/19 200 = 52µs

Data rate 19 200

Transmitter active

Set the speed to 187.5 kbit/s

10x52µs = 520µs

↵

Example 19 200 bit/s

*) For other speeds please contact

Westermo

**) For additional units please contact

Westermo

S1:3 not used