Hints

The MA-45 uses the RS-422/485 interface. RS-422/485 was designed for multidrop appli-
cations. When a system is installed it should form a bus structure (see diagrams). Star 
shaped networks should never be created, there are other Westermo products designed 
to work in star net applications. To install correctly, an RS-422/485 network should be 
terminated at the correct points. The recommendation is to terminate the receiver on 
the master unit and the final bus slave unit. See diagrams for details of how this is done 
with RS-485 (2 wire) and RS-422 (4 wire).
   The line transmitter used in the MA-45 is activated by data received on the RS-232 
interface, unlike conventional converters that rely on a control signal (e.g. RTS).
If any problems do occur on set up of the MA-45, the LED’s will be helpful.
• PWR:  The unit has power.
• RD: 

Data received on the RS-422/485 interface.

• CTS:  Follows RTS
• RTS: 

Status of RTS from the RS-232 interface

• TD: 

Data received on RS-232 interface

N.B.   R+/R–, T+/T– definitations are not standard, it can help to shift A and B  

if the unit does not work.