6193-4201

How a Link connection is lost

The RM-80 will reset the Link if:

… Excessive retries:

When a RM-80 unit transmit a wireless message to another unit, the destination unit
will transmit back an acknowledgment. If the source unit does not receive an acknowl-
edgment, it will re-send the message – this is known as a “re-try”. Both Access Point
and Client will drop the link if the number of retries for a single packet exceeds (7)
times. Packets are retransmitted according to an increasing time delay between retries,
with each attempt on a different frequency.

… Inactivity:

During periods of inactivity, Clients will periodically check that the link to the Access
Point remains intact. This process is called “reassociation”, and will occur approxi-
mately (6) beacon intervals after the last packet was sent to the Access Point. If a
Client unit does not get a response from its Access Point, it will retry the reassociat-
ing request (7) times before resetting the link. If an Access Point does not receive any
traffic from a Client, including reassociating requests, within (12) beacon intervals, the
Access Point will reset the link.

After a Client has reset it’s Link status, it will start scanning for an Access Point, as if it
has just started up.

LED Indication

The following table details the status of the indicating LEDs on the front panel under
normal operating conditions.

LED Indicator

Condition

Meaning

OK GREEN

Normal

Operation

OK

RED

Supply voltage too low.

Radio RX

GREEN flash

Radio receiving data

Radio RX

RED flash

Weak radio signal

Radio TX

Flash

Radio Transmitting

Radio LINK

On

On when a radio communications link is established

Radio LINK

Off

Communications failure or radio link not established

Radio LINK

GREEN flash

RED flash

Serial Port Receiving

CTS low

LAN

ON

Link Established on Ethernet port

LAN

Flash

Activity on Ethernet port.

Serial

GREEN flash

RS-232 Serial Port Activity

Serial

RED flash

RS-485 Serial Port Activity

DIO

On

Digital Output ON or Input is grounded.

DIO

Off

Digital Output OFF and Input is open circuit.

The Ethernet RJ45 port incorporates two indication LEDs. The LINK LED comes on
when there is a connection on the Ethernet port, and will blink off briefly when activity is
detected on the Ethernet Port. The 100MB LED indicates that the connection is at
100 MBit/Sec. The 100MB LED will be off for 10MB/Sec connection.

Other conditions indicating a fault are described in Chapter Six Troubleshooting.