7.1.2

Manual calibration

To set the flowrate constant manually, calculate and set the correct constant using the following formula:

[amount measured by device]

[actually delivered quantity]

Calibration

Man. calibration

Auto calibration

600

1) Access Manual calibration menu (Setup menu > Calibration > Man. calibration).

In Calibration menu, selecting Manual calibration, under the item the curren-
tly set constant will be displayed.
Press

OK

key to access value modification.

Flowrate constant

Min value

Max value

C

1

50000

B

D

A

0600

0

2) Using the suitable keys, set the value of the flowmeter constant:

A)

Press to toggle from one digit to another

B)

Press in succession to modify the value of the digit highlighted by the cursor

C)

Press to save changes or

D)

Press to exit current page without confirming

changes. Refer to the label on the body (Fig. 37).

The flowmeter body must be assembled with the arrow on the label
facing the flow direction.

CODE

Approximate constant

4627405A

250

4627506A

132

4627707A

64

APPROXIMATE CONSTANT

XXX

APPRO

XIMAT

E CON

STANT

XXX

7.2

Flowrate alarms

Set the minimum and maximum values beyond which the display must show an alarm message.

Flowrate alarms

Min flow alarm

Max flow alarm

6.00/min

1) Access Flowrate alarms menu (Setup menu > Flowrate alarms).

Min. and max. flowrate alarms setting is done in the same way.

Under the selected item, the currently set value will be displayed.
Press

OK

key to access modification of the selected item.

Min flow alarm

Min value

Max value

0.1

99999.9

OFF

o

2) To activate the alarm, press

and

keys at the same time until the

message

OFF disappears and flowrate alarm value is displayed.

Carry out the same procedure to deactivate flowrate alarm again.

Min flow alarm

Min value

Max value

C

0.1

99999.9

B

D

A

0040.0

0

l/min

o

3) Set flowrate alarm value:

A)

Press to toggle from one digit to another

B)

Press in succession to modify the value of the digit highlighted by the cursor

C)

Press to save changes or

D)

Press to exit current page without confirming

changes.

Fig. 35

Fig. 36

Fig. 37

Fig. 38

Fig. 39

Fig. 40

x [constant indicated on flowmeter body]

Tab. 6

SETUP