For the temperature and humidity requirements of the wireless switch,

see

Table 3

.

Table 3 Temperature/humidity requirements

Temperature Relative

humidity

0°C to 45°C (32°F to 113°F)

5% to 95%, noncondensing

Cleanness

Dust buildup on the chassis may result in electrostatic adsorption, which

causes poor contact of metal components and contact points, especially
when indoor relative humidity is low. In the worst case, electrostatic

adsorption can cause communication failure.

Table 4 Dust concentration limit in the equipment room

Substance

Concentration limit (particles/m

3

)

Dust particles

≤ 3 x 10

4

(No visible dust on desk in three days)

NOTE:

Dust particle diameter ≥ 5 μm

The equipment room must also meet strict limits on salts, acids, and

sulfides to eliminate corrosion and premature aging of components, as

shown in

Table 5

.

Table 5 Harmful gas limits in an equipment room

Gas Max.

(mg/m

3

)

SO

2

0.2

H

2

S 0.006

NH

3

0.05

Cl

2

0.01