HEIDENHAIN TNC 370D User Manual
Page 42

X23 Power supply at the analog inputs
Terminal Assignment
1
+24 Vdc (IEC 742 EN 50 178, 5.88 low-voltage electrical separation)
2 0
V
X19,X20,X21,X22 Connection for Pt 100 on the PL 410 B
Terminal Assignment
1
I + Constant current for Pt 100
2
U + Measuring input for Pt 100
3
U – Measuring input for Pt 100
4
I – Constant current for Pt 100
5 Shield
Connection to the analog inputs
Connecting cable 2 x 0.14 mm
2
shielded, max. 50 m.
Connection to the inputs for Pt 100 thermistors
The connection to the Pt 100 thermistors must be arranged as a four-wire circuit.
e.g. PL 410 B X19:
1
2
4
5
Measuring input U+
Measuring input U–
→
I+
→
I–
Pt100
Customer´s cable
4 x 0.14 mm
2
screened, max 50 m
3
July 02
Mounting and Electrical Installation
TNC 370 D
3–39