9  Troubleshooting

SMA Solar Technology AG

48

SI30M-44M-60H-80H-BE-en-30

Operating Manual

F 141 InvVtgLo

2

The voltage at connection AC1 of

the master is too low due to AC

sources in the system.

•

Ensure that the Sunny Island is

functional. For this, disconnect all

AC sources and loads from the

Sunny Island and restart the

Sunny Island.

•

Find the cause of the undervoltage

through measurement and

step-by-step connection of the AC

sources and loads.

W 142 InvVtgLoSlv1

1

The voltage at connection AC1 of

slave 1 is too low due to AC

sources in the system.

W 143 InvVtgLoSlv2

1

The voltage at connection AC1 of

slave 2 is too low due to AC

sources in the system.

F 158 VtgOnAC1Det

2

The master has measured an

undesired voltage at connection

AC1.

A bypass switch may have bridged the

internal transfer relay.

• Ensure that the bypass switch is in

the position for operation with the

Sunny Island.

•

Ensure that the Sunny Island is

functional. For this, disconnect all

AC sources and loads from the

Sunny Island and restart the

Sunny Island.

A voltage source (e.g., generator) may

have been connected to the

connection AC1.

•

Disconnect voltage source from

connection AC1 and connect to

connection AC2 (see the

Sunny Island inverter installation

manual).

W 159 VtgOnAC1DetSlv1

1

Slave 1 has measured an

undesired voltage at connection

AC1.

W 160 VtgOnAC1DetSlv2

1

Slave 2 has measured an

undesired voltage at connection

AC1.

F 162 OvrCurDet

2

Too much current is flowing

through the DC connection of the

master.

• Reduce the power of the loads.

W 163 OvrCurDetSlv1

1

Too much current is flowing

through the DC connection of

slave 1.

W 164 OvrCurDetSlv2

1

Too much current is flowing

through the DC connection of

slave 2.

F 166 Overload5min

3

The five minute overload capacity

of the master has been exceeded.

W 167 Overload5minSlv1

1

The five minute overload capacity

of slave 1 has been exceeded.

W 168 Overload5minSlv2

1

The five minute overload capacity

of slave 2 has been exceeded.

No.

Name

Level Cause

Corrective measures