9  Troubleshooting

SMA Solar Technology AG

60

SI30M-44M-60H-80H-BE-en-30

Operating Manual

F 743 CANCom

3

Internal device CAN communication

of the master is disturbed.

•

Ensure that the terminators in the

communication bus are attached.

•

Ensure that undamaged CAT5e

cables are used for communication

and that the cables are plugged in

correctly.

• Contact the SMA Service Line.

W 744 CANComSlv1

1

Internal device CAN communication

of slave 1 is disturbed.

W 745 CANComSlv2

1

Internal device CAN communication

of slave 2 is disturbed.

W 747 InvTmpSnsSlv1

1

Temperature sensor on the

transformer of slave 1 is defective.

• Contact the SMA Service Line.

W 748 InvTmpSnsSlv2

1

Temperature sensor on the

transformer of slave 2 is defective.

W 750 InvTmpSnsSlv1

1

Temperature sensor on the heat sink

of slave 1 is defective.

W 751 InvTmpSnsSlv2

1

Temperature sensor on the heat sink

of slave 2 is defective.

W 753 DateInvalid

1

System time is invalid.

• Select the parameter 250.02 Dt

and set the date. Select the

parameter 250.03 Tm and set the

time.

F 754 BoxCom

2

Communication with Multicluster Box

is interrupted.

•

Ensure that undamaged CAT5e

cables are used for communication

and that the cables are plugged in

correctly.

•

Ensure that the communication bus

is equipped with a terminator at

both ends.

W 755 LoBatMod1

1

Battery protection mode protects the

battery. Level 1 is active.

• Disconnect the loads, start the

generator, start the Sunny Island

and charge the battery.

W 756 LoBatMod2

1

Battery protection mode protects the

battery. Level 2 is active.

W 757 LoBatMod3

1

Battery protection mode protects the

battery. Level 3 is active.

F 758 McNoVtg

2

Voltage of the main cluster cannot be

measured at the master.

• Ensure that all circuit breakers of

the Sunny Island inverters in the

Multicluster Box are closed.

•

Ensure that the cabling at

connection AC1 is correctly

installed.

W 759 McNoVtgSv1

1

Voltage of the main cluster cannot be

measured at slave 1.

W 760 McNoVtgSlv2

1

Voltage of the main cluster cannot be

measured at slave 2.

No.

Name

Level Cause

Corrective measures