9  Troubleshooting

Operating Manual

SI30M-44M-60H-80H-BE-en-30

61

W 778 DSPNoSlv1

1

CAN communication with slave 1 is

faulty.

•

Ensure that undamaged CAT5e

cables are used for communication

and that the cables are plugged in

correctly.

•

Ensure that the communication bus

is equipped with a terminator at

both ends.

W 779 DSPNoSlv2

1

CAN communication with slave 2 is

faulty.

F 781 SlvError

4

Error at a slave in the main cluster

causing system shutdown.

•

Read off the pending and logged

warnings and errors and eliminate

the causes.

F 782 AIVtgMonFail

4

Monitoring of the utility grid has

failed.

• Contact the SMA Service Line.

F 783 CANCom

2

Synchronization in the cluster is

interrupted at the master.

•

Ensure that undamaged CAT5e

cables are used for communication

and that the cables are plugged in

correctly.

•

Ensure that the communication bus

is equipped with a terminator at

both ends.

W 784 CANComSlv1

1

Synchronization in the cluster is

interrupted at slave 1.

W 785 CANComSlv2

1

Synchronization in the cluster is

interrupted at slave 2.

F 787 VcoreFail

3

Internal device voltage in the master

is outside the tolerance limits.

• Contact the SMA Service Line.

F 788 VcoreFailSlv1

3

Internal device voltage in slave 1 is

outside the tolerance limits.

F 789 VcoreFailSlv2

3

Internal device voltage in slave 2 is

outside the tolerance limits.

W 791 RsDspSlv1

1

Signal processor has performed a

reset.

W 792 RsDspSlv2

1

W 793 TimeOutDspSlv1

1

Time for performing a particular task

has been exceeded.

W 794 TimeOutDspSlv2

1

W 797 AiVtgMonFailSlv1 1

Monitoring of the utility grid has

failed.

W 798 AiVtgMonFailSlv2 1

No.

Name

Level Cause

Corrective measures