4 transformer compact station 1000sc, Transformer compact station 1000sc – SMA TCS 500-SC User Manual

Page 33

Advertising
background image

SMA Solar Technology AG

9 Technical Data

Installation Manual

TCS-IT-IEN103610

33

Dimensions and Weight

Climatic Conditions

Options

9.4 Transformer Compact Station 1000SC

Medium-voltage side

Width x height x depth
with medium-voltage switchgear

3 280 mm x 2 550 mm x 2 500 mm

Width x height x depth
without medium-voltage switchgear

2 380 mm x 2 550 mm x 2 500 mm

Weight with medium-voltage switchgear

15.0 t

Weight without medium-voltage switchgear

10.6 t

Degree of protection

*

As per EN 60529

IP23

Operation temperature range

− 20°C … +45°C

Relative humidity, non-condensing

15% … 95%

Maximum operating altitude above sea level
(MSL)

1 000 m

Internal power supply transformer

*

Additional power classes available on request.

6 kVA

Medium-voltage switchgear

None / RE-T / C-C-T

Low-voltage switchgear

1 x LV/HRC switch-disconnector /

1 x circuit breaker

Pre-assembled cable set

5 m / 7.5 m / 10 m / 15 m

Communication distribution box

Communit

Low-voltage meter

GSE meter

Rated power (@ 25°C)

P

ACnom

1 100 kVA

AC nominal power (@ 45°C)

P

AC

1 000 kVA

AC nominal voltage

V

ACnom

15 kV / 20 kV

AC voltage range

V

AC

13.5 kV … 16.5 kV / 18 kV … 22 kV

Rated grid voltage

V

AC

20 kV

Rated grid frequency

f

AC

50 Hz

Nominal current

I

nom

28.9 A

Advertising