9 Technical Data
General
AS-BOX-L
Number of phases
3-phase
Nominal voltage
202 to 253 V
Nominal frequency
45 to 55 Hz
Number of Sunny Backups
3 x Sunny Backup 5000
Mounting type
Suspended
Permitted grid structure (grid side/load side)
TN-C / TN-S
Consumer load connection
Nominal output power/current during grid operation
44 kW / 3 x 63 A
Maximum cable cross section
(suitable for connection)
16 mm
2
Fuse (maximum to be used)
D02 (63 A)
Clamping position
Fuse/spring-type terminals
Consumption meter connection
Nominal output power/current
44 kW / 3 x 63 A
Maximum cable cross section
(suitable for connection)
16 mm
2
Clamping position
Spring-type terminals
PV system connection
Nominal output power/current
30 kW / 3 x 44 A
Maximum cable cross section
(suitable for connection)
16 mm
2
Clamping position
Spring-type terminals
Feed-in meter connection
Nominal output power/current
30 kW / 3 x 44 A
Maximum cable cross section
(suitable for connection)
16 mm
2
Clamping position
Spring-type terminals