Technical Data
SMA Solar Technology AG
44
AS-BoxL-IEN084410
Installation Guide
Sunny Backup connection
Nominal output power/current
15 kW / 3 x 22 A
Maximum cable cross section
(suitable for connection)
6 mm
2
Fuse
C 32 A
Clamping position
Fuse/spring-type terminals
Generator connection (optional)
Nominal output power/current
30 kW / 3 x 44 A
Maximum cable cross section
(suitable for connection)
16 mm
2
Fuse (maximum to be used)
D02 (35 A)
Clamping position
Fuse/spring-type terminals
Power consumption
Internal consumption during the day
114 W
Internal consumption at night
69 W
Certificates
Independent disconnection device per
DIN VDE 0126-1-1
Yes, in combination with the
Sunny Backup 5000
EC Declaration of Conformity
Enclosed, download area www.SMA.de/en
Mechanical data
Dimensions (W x H x D in mm)
600 x 760 x 210
Weight
41 kg
Ambient Conditions
Ambient temperature
–25 to +50 °C
Air humidity
0 to 100 %
Protection Rating
Protection class according to DIN EN 60529