Installation Manual

9.3.2 Checking the Function of the Varistors

Varistors are wear parts. Their functional efficiency diminishes with age or repeated strain as a result
of overvoltage. It is therefore possible that one of the thermally monitored varistors has lost its
protective function.

You can check the function of the varistors as follows:

1. Open the inverter as described in Section 7.2 "Opening the Inverter" (page 57).
2. Use a multimeter to check that all the installed

varistors have a conductive connection between
connectors B and C.

Position of varistors
The position of the varistors can be determined with the help of the diagram below.
Observe the following assignment of the terminals:

• Terminal A: outer terminal with loop

(varistor connection with crimp)

• Terminal B: middle terminal
• Terminal C: outer terminal with loop

(varistor connection without crimp)

Result

Measure

There is a conductive connection.

There must be a different error in the inverter.

• Close the inverter as described in

Section 7.3 "Closing the Inverter" (page 59).

• Contact the SMA Service Line.