Added Parameters:

This software does not add any new parameters to the drive.

Changed Parameters:

Refer to Appendix 1 ot the GPD 515 Technical Manual, TM 4515. The following changes result from
the installation of this software in the drive.

Parameter

Function Name

Changed

Standard

Continuous

Software

DB Software

L8-01

Internal Dynamic Braking

Max. Value

1

3

Transistor Protection

Factory Setting

0

3

L 8 - 0 1 : Internal Dynamic Braking

Factory setting: 3

Resistor Protection

Range: 0 to 3

This parameter sets both the level of protection (based on duty cycle) and whether

the dynamic braking transistor will be active when the drive is not running.

L8-01

Resistor Over-

Duty Cycle

Dynamic Braking

Setting

load Protection

(1)

Transistor Active

(2)

0

Disabled

N/A

During Run

1

Enabled

10%

During Run

2

Enabled

3%

All of the time

3

Enabled

10%

All of the time

(1)

Duty Cycle is based on 6 minute interval.

(2)

When bus voltage exceeds the DB turn on level.

Deleted Parameters:

This software does not delete any parameters from the drive.

Startup Procedure:

Use the appropriate startup procedure in Section 2 of the GPD 515 Technical Manual (TM 4515).