Yaskawa G5 Output Voltage PID User Manual
Page 5
 
Date: 07/01/04, Rev: 04-07
Page 5 of 6
TM.G5SW.022
P1-04
PID Integral Limit
A - - -
PID I Limit
P1-04= 100.0 %
 
Sets the maximum limit of the accumulated integral error. 
 
 
P1-05
PID Derivative Time
A - - -
PID D Time
P1-05= 0.00 Sec
 
Sets the PID response based on how quickly the voltage feedback varies. 
 
 
P1-06
PID Limit
PID Limit
A - - -
PID Limit
P1-06= 100.0%
 
Sets the maximum output from the PID. 
 
 
P1-07 PID
Offset
A - - -
PID Offset
P1-07= 0.0%
 
This value is added to the PID output. 
 
 
P1-08
PID Delay Time
A - - -
PID Delay Time
P1-08= 0.00 Sec
 
Delays the PID output. 
 
 
P1-09
Vref Accel Time
A - - -
Vref Rate Time
P1-09= 0.20 Sec
 
Sets the rate that the PID will increase the output voltage. 
Setting Range
0.0 to 100.0%
Factory Default: 100.0% 
Modbus Address: 0x583 
Setting Range
0.00 to 10.00 Seconds
Factory Default: 0.00 Sec 
Modbus Address: 0x584 
Setting Range
0.0 to 100.0%
Factory Default: 100.0% 
Modbus Address: 0x585 
Setting Range
0.0 to 100.0%
Factory Default: 0.0% 
Modbus Address: 0x586 
Setting Range
0.00 to 10.00 Seconds
Factory Default: 0.00 Sec 
Modbus Address: 0x587 
Setting Range
0.00 to 2.00 Seconds
Factory Default: 0.20 Sec 
Modbus Address: 0x588